Värmebaronen EK 15E
menu
s
Menu - Advanced Service level
External control with 0-10V signal
, adjustment.
0: Output limiting. The electric flow heater's temperature control is superior; the setpoint must
be set slightly higher than the required temperature.
1: Output control, only the overtemperature limit restricts.
See "Advanced Service level" rows 16 and 17.
0
Maximum output
upon restart after power failure, 6 kW directly exceeding connection delay, adjustment.
1: No connection delay.
2: One hour.
3: Two hours.
2
Select,
fixed setpoint or UTK
- function, adjustment
0: Fixed setpoint
1: UTK
0
Maximum boiler temperature, method
, adjustment.
0: Absolute temperature.
1: Temperature relative to setpoint.
0
Maximum boiler temperature - adjustment
6-95°C
This setting is used by both methods according to row 16 above.
At "Absolute temperature", the selected temperature should not exceed 10°C.
10
Manual activation
of rows 19 and 20. Adjustment
0: Off
1: Limited to 15 minutes
0
Manual activation / test run of output stage
- 0-7, adjustment, see row 18
+/- to step in / out output stage.
Manual output connection is subordinate to all protective functions, i.e., if the load guard function
or overtemperature protection alarm is activated, the electric flow heater will step down in the
same way as for automatic operation.
0
Manual circulation pump
, adjustment, see row 18.
0: Circulation pump off
1: Circulation pump on
0
-
-
Control of circulation pump
- operation mode, adjustment.
0: Circulation pump follows output stage
The pump only starts when the first output stage is connected. The pump stops 30 minutes after the
electric flow heater becomes inactive. The circulation pump is run for two minutes every other day.
1: Circulation pump always on
1
Current
temperature of power circuit board
, display.
Delivery setting