Värmebaronen EK 15E

Read these instructions carefully before installation 

and operation!
Keep these instructions at the electric flow heater!
Check that the electric flow heater has not been 

damaged during transport. Report any transport 

damage to the carrier.
Check that the delivery is complete.
All installation must be performed by an authorised 

person in accordance with the existing regulations.
Never disable the safety equipment!
The electric flow heater must never be switched off 

electrically unless the heating system is full and the 

flow heater vented.
Correct installation in combination with correct 

adjustment and continuous service will produce high 

operational reliability and good heating economy.
The electric flow heater must not be modified, changed 

or converted in any way.
Only authorised persons may carry out work on the 

electric flow heater.
Ensure the power to the electric flow heater is switched 

off before service / repair.
Never carry out maintenance work / service on 

pressure-bearing parts when they are pressurised.

The electric flow heater may not be used by children 

or people with physical or mental impairments. 

Nor by children / people who lack knowledge about 

the electric flow heater.
Children may not play with the electric flow heater 

and connect accessories.
Always contact your installation engineer for service.
The type and manufacturer's number of the electric 

flow heater must always be specified when contacting 

Värmebaronen. See the rating plate

Värmebaronen AB reserves the right to change the 

specification, in accordance with its policy of continuous 

improvement and development, without prior notice.
The following icons are used in these instructions 

to indicate important information:

  

Information that is important for optimum 

operation.

  

Tells you what you should or should not do 

to avoid personal injury.

  

Tells you what you should or should not do to 

prevent a component, the electric flow heater, 

a process or the environment from being 

damaged or destroyed.

  

Electrical hazard!

Safety and handling

Function

Electric flow heater EK 15

Output 14.7 kW, divided into seven 2.1 kW stages, which are 
controlled via an electronic temperature control, 20-95°C.
Can easily be climate controlled.
Load guard with current transformers included.
All-pole switch.
Operation / status indication.
Stainless electric flow heater.

 Connection for external blocking connection or output 

control 0-10V.
Output signal for external display of connected output.
Overheating protection with alarm indication.
 A low water volume and well-insulated tank mean 
low heat loss.
Brackets for wall mounting included.
Compact format.

Simple connection

Mounted on the wall with included brackets.
Has connection for front / safety line on top, return line 
is on the bottom.

Temperature control

The temperature control regulates output connection in 
seven stages.
Available accessories include an outdoor temperature sensor, 

which allows the temperature of the electric flow heater to 
be determined by the outdoor temperature and the selected 

heat curve, UTK. A room unit is also available that, when 
used with the UTK function, increases heating comfort at 

the lowest possible energy consumption by utilising passive 

heat from, e.g., solar radiation. The unit also reduces 
variations in room temperature caused by wind.
The electronic controls contain an over temperature function, 

which switches off selected output if the boiler temperature 

exceeds the setpoint with an adjustable value. When the over 
temperature ceases, the output is automatically reconnected.
When any of these functions take effect, the status indicator 
blinks to indicate this.

Accessories

Outdoor temperature sensor

Room device.

Содержание EK 15 E

Страница 1: ...Installation and maintenance EK 15 E Electric flow heater 7 stage 14 7 kW 1212_EK15E_191017_en pwr 1 14 1 15 dsp 1 05 p typ 4...

Страница 2: ...sator setpoints UTK Alternative temperature Alternative temperature with room unit Optional Room Unit Over temperature protection Overheating protection Action in the event of a risk of freezing Frost...

Страница 3: ...onthat is important for optimum operation Tells you what you should or should not do to avoid personal injury Tells you what you should or should not do to prevent a component the electric flow heater...

Страница 4: ...the value is changed the indicator flashes The new value is only applied after confirming by pressing The old value is removed if the row is left with or User level Reading and modification of the mos...

Страница 5: ...rent alarm codes according to a rolling schedule Once the cause of the alarm is resolved and is acknowledged with OK the red indicator stops flashing The display will return to its normal display Ackn...

Страница 6: ...rve parallel displacement 5 30 adjustment 20 UTK function switched off see Advanced Service Level row 15 Curve higher value provides warmer temperatures for cold outdoor temperatures 20 60 adjustment...

Страница 7: ...time to stabilize UTK function switched off see Advanced Service Level row 15 Alternative temperature 15 15 C Adjustment See Outdoor temperature sensor and alternative heating in Electrical installat...

Страница 8: ...ut 2 1 4 2 6 3 8 4 10 5 12 6 14 7 kW Current 3 6 05 9 1 12 1 15 1 18 1 21 2 A 7 UTK function switched off see Advanced Service Level row 15 UTK min Limitation of the supply line temperature Adjustment...

Страница 9: ...16 above At Absolute temperature the selected temperature should not exceed 10 C 10 Manual activation of rows 19 and 20 Adjustment 0 Off 1 Limited to 15 minutes 0 Manual activation test run of output...

Страница 10: ...see Advanced Service Level line 14 For testing and service the connection delay and output connect disconnect can be temporarily sped up see Service level rows 1 and 2 The electric flow heater should...

Страница 11: ...few more times The pressure in a heating system varies with the temperature Do not add water unnecessarily Draining If the heating system needs to be drained of water the electric flow heater must fi...

Страница 12: ...ontain corrosion limiting additives Suitable water line quality Alkalinity 60 mg l to avoid corrosion Carbonic acid content 25 mg l increase the risk of corrosion Sulphate contents 100 mg l may accele...

Страница 13: ...and must be laid so that water pockets cannot form The opening pressure of the safety valve is determined by the component in the system that tolerates the lowest pressure System principles The figure...

Страница 14: ...conductor is connected in terminal 4 10 Electrical installation Electrical installation shall be carried out in accordance with the applicable regulations by an authorized electrical installer or by...

Страница 15: ...er 14 Overheating protection 15 Contactor power group three 16 Heating element output group three 8 4 kW 17 Heating element for output group two 4 2 kW 18 Heating element for output group one 2 1 kW W...

Страница 16: ...ain only when the temperature has dropped below the limit Selectable in Advanced Service level rows 16 and 7 Low boiler temperature Boiler temperature lower than 7 C The electric flow heater s tempera...

Страница 17: ...ard during resistance measurement When the boiler is energized voltage is measured in the sensor s connection points at the PCB Boiler temperature C k V C k V C k V 5 141 9 4 7 40 30 3 7 75 8 2 2 3 10...

Страница 18: ...tage size 2 1 kW Current stage 3 A Ingress protection rating IP x1 Flow requirements recommended t 10 C min max t 25 5 C 0 35 0 2 0 7 litres sec litres sec Pressure drop Volume 3 6 litres Design press...

Страница 19: ...panel 1 700414 Overlay 1 6 210206 Temperature sensor 1 11 440090 Capacitor 1 12 130010 Switch 1 120009 Knob for switch 1 700223 Shaft for switch 1 13 180023 Miniature circuit breaker 1 14 120025 Over...

Страница 20: ...V rmebaronen AB Arkelstorpsv gen 88 SE 291 94 Kristianstad Tel 46 44 22 63 20 www varmebaronen se www varmebaronen com info varmebaronen se...

Отзывы: