Värmebaronen EK 15E
menu
s
Menu - User Level
Initial values
Dimensioned values,
select a curve that provides the desired supply line temperature.
Unknown values - floor heating systems,
Select a curve that provides a temp. of 40°C for wooden
joists and 30°C for concrete slab in the supply line temperature on the coldest day.
Unknown values - Radiator system,
select a curve that provides a 55°C supply temperature for a low
temperature system on the "coldest day" and a 70°C supply temperature for a high temperate system.
The 'coldest day' is the lowest temperature that normally occurs in the location.
Adjustment of basic setting
For low temperatures, select a higher level. An increase in the room temperature can be limited
by the thermostats for the radiators or underfloor heating.
For high temperatures, select a lower level.
If the room is not at the desired temperature, additional adjustment is needed. Wait at least one
day between adjustments so that temperatures have time to stabilize.
UTK function switched off, see Advanced Service Level row 15.
Alternative temperature
- -15-+15°C Adjustment
See "Outdoor temperature sensor and alternative heating" in "Electrical installation".
Closed input activates the function. Can be used for night-time reduction, holiday mode or similar,
see "Electrical installation"; "Alternative temperature".
Function without installed room unit: Shifts, parallel displacement, UTK curve level with a configurable
number of stages. This corresponds to a change in the room temperature by the approximate
corresponding number of degrees.
-5
Room unit not installed.
Room unit, current room temperature
in whole degrees. 15-25°C, display
Room unit not installed.
Room unit, set temperature
in whole degrees 15-25°C, display.
Adjustments are made using the room unit.
ECO-mode
, adjustment
Standby mode, the electric flow heater holds at a temperature of 7°C.
The pump is turned off but is run every other day.
0: Off
1: On, the electric flow heater holds at a standby temperature of 7°C. The circulation pump is run every
other day for two minutes. Output is allowed to step in if external restriction and load guard allow.
0
Delivery setting