Värmebaronen EK 15E
Menu - User Level
Current boiler temperature
, display.
Desired boiler temperature
, setpoint, 20-95°C, adjustment
For electric flow heaters with UTK, a calculated boiler temperature setpoint is displayed.
20
Current number of connected output stages
, 0-7, display
Step
1
2
3
4
5
6
7
Power output
2.1
4.2 6.3 8.4 10.5 12.6 14.7
kW
Current level for external 0-10V control signal
, 0-100%, display
Current electrical current
, amps, in the highest load phase, 0-50 A, display
Requires that the current transformers are connected.
UTK function switched off, see Advanced Service Level row 15.
Current outdoor temperature
, °C, requires outdoor temperature sensor -50-50°C, display
UTK function switched off, see Advanced Service Level row 15.
UTK, alternative temperature input status
, display.
0: Not active.
1: The function is active, see "User level" row 9.
0
UTK function switched off, see Advanced Service Level row 15.
Level curve
, parallel displacement, 5-30, adjustment
20
UTK function switched off, see Advanced Service Level row 15.
Curve
, higher value provides warmer temperatures for cold outdoor temperatures, 20-60, adjustment
38
The flow temperature is calculated according to the current outdoor temperature, settings for the curve and
level and room temperature. The supply line temperature can be min / max limited.
10
20
30
40
50
60
70
80
-30
-20
-10
0
10
20
F 50
F 40
F 30
°C
°C
The diagram shows the curves F30, F40 and F50 at Level = 20.
Curve F30 aims for a supply temperature of 30°C at an outdoor temperature of ±0°C. The corresponding
temperatures for curves F40 and F50 are 40°C and 50°C respectively.
The vertical axis shows the supply line temperature and the horizontal axis shows the outdoor temperature.
Heating curve
The heating system's dimensioned supply line temperature is used as the initial value. If the value is not
known, general values are used. If the room is not at the desired temperature, additional adjustment is needed.
Wait at least one day between adjustments so that temperatures have time to stabilize.
Delivery setting