Modbus Implementation
Tank Gauge Transmitter
50
Installation and Operations Manual
Note!
In all of the following communication examples, the error check value is dependent
upon the mode of transmission.
9.5.1
Integer Data
The integer data is a whole number between 0 and the maximum Modbus integer
(inclusive). The maximum Modbus integer is a user-configurable variable that is a whole
number between 0 and 65,535 (inclusive). The integer data must also be scaled for each
data type by entering the desired units, a minimum, and a maximum value. In order for
the integer value to be correctly interpreted, these scaling factors must match the
format expected by the host system. Scaling of the integer parameters is accomplished
through floating-point registers or by using the Model 1200 Handheld Interface.
The following communication example shows the request for one register starting at
register 0 (0000 Hex).
For the following example, assume:
•
minimum = 1 meter
•
maximum = 15 meters
•
maximum Modbus integer = 65,534
Status Bit (L)
Low-order data address byte of the first bit to read or write
Error Check
Message checksum CRC (Cyclical Redundancy Check)
Term
Definition
Host Request
Address
Function
Code
Start Reg
H
Start Reg
L
# of Reg
H
# of Reg
L
Error
Check
01
03
00
00
00
01
XX
ATT Response
Address
Function
code
Byte
Count
Data
MSB
Data
LSB
Error
Check
01
03
02
41
24
XX
Содержание Network Adapter 4000
Страница 2: ......
Страница 6: ...Advanced Technology Transmitter iv Installation and Operations Manual...
Страница 46: ...Specifications Tank Gauge Transmitter 36 Installation and Operations Manual...
Страница 48: ...Ordering Information Tank Gauge Transmitter 38 Installation and Operations Manual...
Страница 54: ...Theory of Operation Tank Gauge Transmitter 44 Installation and Operations Manual...
Страница 72: ...Modbus Implementation Tank Gauge Transmitter 62 Installation and Operations Manual...
Страница 78: ...Tank Gauge Transmitter 68 Installation and Operations Manual...
Страница 79: ...69 4000 NOTES...