ATT Family of Products
Tank Gauge Transmitter
46
Installation and Operations Manual
8.2
Model 4050 Digital Input/Output Unit
The Model 4050 is a digital I/O unit. It includes four digital contact closure outputs and
four digital inputs. It operates connected to and is powered from the ATTI bus. The unit
is mounted in a round explosion proof junction box. Three 3/4-inch conduit entries are
available.
•
Primarily configured by jumpers. Three sets of jumpers are used.
•
Unit address: 4 jumpers for range 0-15. Digital I/O units normally use address 4,5
or 6.
•
Active state jumper for each digital output. Jumper determines if contact is N. O. or
N. C.
•
Default power condition for each digital output. Jumper determines if contact is
open or closed when no power is applied.
8.2.1
Digital Outputs
The use of the digital outputs is configured within the ATT using the handheld interface.
Digital outputs 1 - 4 can be configured as follows:
1. Set output as level switch:
•
Set for low or high closure.
•
Set level to actuate.
2. Set output for Modbus command to write.
8.2.2
Digital Inputs
Digital inputs 1 - 4, can each be read with a Modbus command.
8.2.3
Relay Specifications
The latching relays will switch 110 VAC at 1 A or 24 VDC at 2 A. The unit does not
support 220/230 VAC.
Содержание Network Adapter 4000
Страница 2: ......
Страница 6: ...Advanced Technology Transmitter iv Installation and Operations Manual...
Страница 46: ...Specifications Tank Gauge Transmitter 36 Installation and Operations Manual...
Страница 48: ...Ordering Information Tank Gauge Transmitter 38 Installation and Operations Manual...
Страница 54: ...Theory of Operation Tank Gauge Transmitter 44 Installation and Operations Manual...
Страница 72: ...Modbus Implementation Tank Gauge Transmitter 62 Installation and Operations Manual...
Страница 78: ...Tank Gauge Transmitter 68 Installation and Operations Manual...
Страница 79: ...69 4000 NOTES...