Tank Gate Interface
60
Installation and Operations Manual
LevelOffset
Specifies the amount of offset to add to the Level. The default is 0.
TempOffset
Specifies the amount of offset to add to the Temp. The default is 0.
LevelDeadband
Specifies the amount of change in the Level that must occur for the level to be
updated each Change of State period. The default is 0.1.
TempDeadband
Specifies the amount of change in the Temp that must occur for the temperature
to be updated each Change of State period. The default is 0.25.
Report
Causes automatic notification to the Host (in response to a Change of State
Request) when the Value changes State. Parameter value can be High, Low or
No. Report=No disables notification. Points with Report = High will be sent
before points with Report = Low. The default is High.
Maxtime
Specifies the maximum time (in secs) between automatic Change of State
responses being sent to the Host. Report must be set to either Low or High for
the Value parameter to be sent in response to a Change of State Request. A
value of 0 disables this option. Non-zero values cause responses to be sent
even if the value has not changed since the last message. The maximum is
65535 seconds. The default is 600.
Watchdog
Enables the watchdog task on the Motherboard. The watchdog task monitors
the MBTX point on the Model 8310 and verifies it is scanning for gauges. If the
8203 Dual RS-485 Communications Interface Module fails, the 0x4000 and the
0x0001 bits of the PntStatus will be set to indicate the failure.
Dynamic Parameters
Function
Command
MBTX Command. Valid values are:
Calibrate: Calibrate the ATT
Cancel: Cancel (4000 ATT only)
Clear Mods: Clear Modifications (4000 ATT only)
Enc Battery Off: Turn off Encode Battery (4000 ATT only)
Restart: Restart ATT (4000 ATT only)
Save to EEPROM: Save the ATT database to EEPROM (4000 ATT only)
Level
Floating point value representing the tank level (Floating point Register 0). The
Level will be presented in decimal feet.
Temp
Floating point value representing the tank temperature (Floating point Register
1). The Temperature will be presented in Fahrenheit.
RTD1
Floating point value representing the RTD resistance, represented in Ohms
(Floating point Register 2).
AlarmStatus
Integer value indicating the Alarm Status (Integer Register 5). Values are:
0x0001: Critical Low Level
0x0002: Advisory Low Level
0x0004: Advisory High Level
0x0008: Critical High Level
0x0010: Critical Low Temperature
0x0020: Advisory Low Temperature
0x0040: Advisory High Temperature
0x0080: Critical High Temperature
0x0100: Hardware Input 1
0x0200: Hardware Input 2
Configuration Parame-
ters
Function
Содержание 8300 series
Страница 2: ......
Страница 6: ...Tank Gate Interface iv Installation and Operations Manual ...
Страница 14: ...Overview Tank Gate Interface 4 Installation and Operations Manual ...
Страница 50: ...Software Description Tank Gate Interface 40 Installation and Operations Manual ...
Страница 52: ...Dual RS 485 MODBUS Software Blocks Tank Gate Interface 42 Installation and Operations Manual ...
Страница 56: ...Tank Gate Interface 46 Installation and Operations Manual ...
Страница 68: ...Tank Gate Interface 58 Installation and Operations Manual ...
Страница 100: ...Tank Gate Interface 90 Installation and Operations Manual ...
Страница 108: ...Dual RS 485 GSI ASCII Software Blocks Tank Gate Interface 98 Installation and Operations Manual ...
Страница 112: ...Tank Gate Interface 102 Installation and Operations Manual ...
Страница 115: ...8303 Installation Varec Inc 105 s Figure 7 2 Tank Gate Interface Dimensions 197 204 125 ...
Страница 148: ...Appendix Order Codes Tank Gate Interface 138 Installation and Operations Manual ...
Страница 149: ......