Software Description
Tank Gate Interface
36
Installation and Operations Manual
the values, MSTX.00.RawValue, MSTX.01.RawValue, ... MSTX.07.RawValue. Setting the Size to 1
does not limit the read to 1 parameter, rather it indicates that block operations will be processed
by stepping through points by incrementing the number, starting with parameter specified by
the PntRef.
4.4.7
Integer Register (IREG)
The Integer Register point provides two bytes of storage. It is often used for inter-
point communications where no other means is provided.
Parameters
The database parameters used by the IREG point are listed and described below:
4.4.8
Modbus Gateway (MODGW)
The Modbus Gateway provides dynamic and statistical information for the
communications between the 8300 series Tank Gate Interface and the Modbus
masters.
Parameters
The database parameters used by the MODGW point are listed and described below:
Configuration Parameters
Function
Tag
A Tag can contain 15 bytes of data and can include any printable ASCII
character. Tags can be used to identify points indicating the use of the
point.
Configuration Parameters
Function
Value
Integer (2 bytes) value
Configuration Parameters
Function
ID
Slave Address that the Modbus Slave protocol handler will respond to. The
default is to match the Unit Address of the 8300 series Tank Gate Interface.
Mode
Operational Mode. The Mode is a hex value, with individual bits controlling
various aspects of the operation of the Modbus Slave protocol handler. The
bits have the following meanings:
0x01 – Set Param Indexing mode
0x02 - Integer Swap mode
0x04 – Swap CRC bytes
0x08 - ASCII mode
0x20 – Wonderware Mode
0x80 - Ignore any trailing nulls in the request
The default is 0.
BaudRate
Baud Rate for communications to the Host system. Valid values are: 1200,
2400, 2400, 9600 and 19200. Changing the BaudRate parameter will
immediately change the configuration of the ComPort.
Содержание 8300 series
Страница 2: ......
Страница 6: ...Tank Gate Interface iv Installation and Operations Manual ...
Страница 14: ...Overview Tank Gate Interface 4 Installation and Operations Manual ...
Страница 50: ...Software Description Tank Gate Interface 40 Installation and Operations Manual ...
Страница 52: ...Dual RS 485 MODBUS Software Blocks Tank Gate Interface 42 Installation and Operations Manual ...
Страница 56: ...Tank Gate Interface 46 Installation and Operations Manual ...
Страница 68: ...Tank Gate Interface 58 Installation and Operations Manual ...
Страница 100: ...Tank Gate Interface 90 Installation and Operations Manual ...
Страница 108: ...Dual RS 485 GSI ASCII Software Blocks Tank Gate Interface 98 Installation and Operations Manual ...
Страница 112: ...Tank Gate Interface 102 Installation and Operations Manual ...
Страница 115: ...8303 Installation Varec Inc 105 s Figure 7 2 Tank Gate Interface Dimensions 197 204 125 ...
Страница 148: ...Appendix Order Codes Tank Gate Interface 138 Installation and Operations Manual ...
Страница 149: ......