Tank Gate Interface
44
Installation and Operations Manual
Report
Causes automatic notification to the Host (in response to a Change of State
Request) when the Level, Temp, Position changes. Parameter value can be High,
Low or No. Report=No disables automatic notification. Points with Report = High
will be sent before points with Report = Low. The default is High.
Maxtime
Specifies the maximum time (in secs) between automatic Change of State
responses being sent to the Host. Report must be set to either Low or High for
the Value parameter to be sent in response to a Change of State Request. A value
of 0 disables this option. Non-zero values cause responses to be sent even if the
value has not changed since the last message. The maximum is 65535 seconds.
The default is 600.
Watchdog
Enables the watchdog task on the Motherboard. The watchdog task monitors the
AT4530 point on the 8203 Dual RS-485 Communications Interface Module and
verifies it is scanning for gauges.
Dynamic Parameters
Function
AvgTemp
IEEE Floating point value representing the average temperature. The data is
returned in the format specified during the configuration of the gauge. The
AvgTemp can be converted from Metric to English (or vice-versa) by setting the
TempConvert parameter of the appropriate MSCAN, RKSCN or WBSCN point.
Vaportemp
Floating point value representing the gas temperature. The data is returned in
the format specified during the configuration of the gauge. The Temperature
can be converted from Metric to English (or vice-versa) by setting the
TempConvert parameter of the appropriate MSCAN, RKSCN or WBSCN point.
Temp1-Temp16
Floating point value representing the product temperature at various levels. The
data is returned in the format specified during the configuration of the gauge.
Temp1-Temp16 can be converted from Metric to English (or vice-versa) by
setting the TempConvert parameter of the appropriate MSCAN, RKSCN or
WBSCN point.
AverageNum
Number of active temperature elements.
Level
Level Data from Varec 6000 Servo Gauge (STG) or 4590 Tank Side Monitor.
ErrorCode
Error Code. Refer to the N453x manual for further explanation.
Status
Hart Command 48 Status. Refer to manufacturer for additional information.
DiagCode
Diagnostic code
CustodyMode
Weights and Measures Status
DeviceStatus
4590 TSM Internal Status
Elapse
Time of last scan.
Interval
Amount of time (in HR:MIN:SEC) between scans of the gauge
Config Parameters
Function
Содержание 8300 series
Страница 2: ......
Страница 6: ...Tank Gate Interface iv Installation and Operations Manual ...
Страница 14: ...Overview Tank Gate Interface 4 Installation and Operations Manual ...
Страница 50: ...Software Description Tank Gate Interface 40 Installation and Operations Manual ...
Страница 52: ...Dual RS 485 MODBUS Software Blocks Tank Gate Interface 42 Installation and Operations Manual ...
Страница 56: ...Tank Gate Interface 46 Installation and Operations Manual ...
Страница 68: ...Tank Gate Interface 58 Installation and Operations Manual ...
Страница 100: ...Tank Gate Interface 90 Installation and Operations Manual ...
Страница 108: ...Dual RS 485 GSI ASCII Software Blocks Tank Gate Interface 98 Installation and Operations Manual ...
Страница 112: ...Tank Gate Interface 102 Installation and Operations Manual ...
Страница 115: ...8303 Installation Varec Inc 105 s Figure 7 2 Tank Gate Interface Dimensions 197 204 125 ...
Страница 148: ...Appendix Order Codes Tank Gate Interface 138 Installation and Operations Manual ...
Страница 149: ......