8303
Software Description
Varec, Inc.
31
a bridge. Other options include assigning one COM point to communicate with a Slave device
while communicating to a Host system on the other.
4.4.3
Floating Point Register (FPREG)
The Floating Register point provides four bytes of storage in IEEE floating point
format. It is often used for inter-point communications where no other means is
provided.
Parameters
The database parameters used by the FPREG point are listed and described below:
4.4.4
Emulator (EMU)
The Emulator point allows the to emulate a Whessoe-Varec Model 6820 Tank
Scanning Unit (TSU). This point provides access for level, temperature data, and
gauge status information from any type of tank gauge interface supported by the
8203 Dual RS-485 Communications Interface Module.
Parameters
The database parameters used by the EMU point are listed and described below:
Configuration Parameters
Function
Tag
Point tag
Dynamic Parameters
Function
Value1 through Value50
Real (4 bytes) value
PntStatus
Integer HEX value indicating status of point. Values are:
0x0001: Gauge Not Responding. The first time the gauge does not
respond, the 0x8000 bit is set. On the second try, the 0x01 bit is set.
0x0002: Data Invalid (General Data Error)
0x0004: Bad Level
0x0008: Temp OverRange
0x0010: Temp UnderRange
0x0020: A/D Error
0x0040: Filtering Level
0x0800: Filtering Temp
Elapse
Time of the last Change of State.
PntCheckSum
CRC-16 Checksum for point’s static Configuration Parameters.
Configuration Parameters
Function
Tag
The point description can contain 30 bytes of data and can include any
printable ASCII character. Descriptions can be used as information relevant
to any aspect of the point, such as its use, location, operating information,
etc. The default description is set to “EMU.00”.
Содержание 8300 series
Страница 2: ......
Страница 6: ...Tank Gate Interface iv Installation and Operations Manual ...
Страница 14: ...Overview Tank Gate Interface 4 Installation and Operations Manual ...
Страница 50: ...Software Description Tank Gate Interface 40 Installation and Operations Manual ...
Страница 52: ...Dual RS 485 MODBUS Software Blocks Tank Gate Interface 42 Installation and Operations Manual ...
Страница 56: ...Tank Gate Interface 46 Installation and Operations Manual ...
Страница 68: ...Tank Gate Interface 58 Installation and Operations Manual ...
Страница 100: ...Tank Gate Interface 90 Installation and Operations Manual ...
Страница 108: ...Dual RS 485 GSI ASCII Software Blocks Tank Gate Interface 98 Installation and Operations Manual ...
Страница 112: ...Tank Gate Interface 102 Installation and Operations Manual ...
Страница 115: ...8303 Installation Varec Inc 105 s Figure 7 2 Tank Gate Interface Dimensions 197 204 125 ...
Страница 148: ...Appendix Order Codes Tank Gate Interface 138 Installation and Operations Manual ...
Страница 149: ......