Tank Gate Interface
48
Installation and Operations Manual
TempDeadband
Specifies the amount of change in the Temp that must occur for the
level to be updated each Change of State period. The default is 0.25.
TempInterleave
Temperature Interleave. Determines how often the temperature is read
from the DAU. The default is 10, which means that every tenth scan of
the DAU, the temperatures will be read.
Report
Causes automatic notification to the Host (in response to a Change of
State Request) when the Value changes State. Parameter value can be
High, Low or No. Report=No disables notification. Points with Report =
High will be sent before points with Report = Low. The default is High.
Maxtime
Specifies the maximum time (in secs) between automatic Change of
State responses being sent to the Host. Report must be set to either Low
or High for the Value parameter to be sent in response to a Change of
State Request. A value of 0 disables this option. Non-zero values cause
responses to be sent even if the value has not changed since the last
message. The maximum is 65535 seconds. The default is 240.
Watchdog
Enables the Motherboard watchdog task for the DAU point. The
watchdog task monitors the DAU point and verifies it is scanning for
devices. If the DAU point stops execution, the PntStatus will be set to
0x4000 to indicate a failure.
Dynamic Parameters
Function
Temp1-Temp14
Floating point value representing the temperature of each temp sensor
configured.
TempFilter
Temp in Liquid parameter. Bits 0 – 13 indicate if Temp sensors 1 – 14
are submerged in liquid. Bit 14 indicates a System Error. Bit 15 indicates
a Temp calibration error.
0x0001: Temp 1 is in Liquid
0x0002: Temp 2 is in Liquid
0x0004: Temp 3 is in Liquid
0x0008: Temp 4 is in Liquid
0x0010: Temp 5 is in Liquid
0x0020: Temp 6 is in Liquid
0x0040: Temp 7 is in Liquid
0x0080: Temp 8 is in Liquid
0x0100: Temp 9 is in Liquid
0x0200: Temp 10 is in Liquid
0x0400: Temp 11 is in Liquid
0x0800: Temp 12 is in Liquid
0x1000: Temp 13 is in Liquid
0x2000: Temp 14 is in Liquid
0x4000: System Error
0x8000: Temp Calibration error
Configuration Parameters
Function
Содержание 8300 series
Страница 2: ......
Страница 6: ...Tank Gate Interface iv Installation and Operations Manual ...
Страница 14: ...Overview Tank Gate Interface 4 Installation and Operations Manual ...
Страница 50: ...Software Description Tank Gate Interface 40 Installation and Operations Manual ...
Страница 52: ...Dual RS 485 MODBUS Software Blocks Tank Gate Interface 42 Installation and Operations Manual ...
Страница 56: ...Tank Gate Interface 46 Installation and Operations Manual ...
Страница 68: ...Tank Gate Interface 58 Installation and Operations Manual ...
Страница 100: ...Tank Gate Interface 90 Installation and Operations Manual ...
Страница 108: ...Dual RS 485 GSI ASCII Software Blocks Tank Gate Interface 98 Installation and Operations Manual ...
Страница 112: ...Tank Gate Interface 102 Installation and Operations Manual ...
Страница 115: ...8303 Installation Varec Inc 105 s Figure 7 2 Tank Gate Interface Dimensions 197 204 125 ...
Страница 148: ...Appendix Order Codes Tank Gate Interface 138 Installation and Operations Manual ...
Страница 149: ......