Tank Gate Interface
54
Installation and Operations Manual
Watchdog
Enables the watchdog task on the Motherboard. The watchdog task monitors
the MBMFT point on the 8203 Dual RS-485 Communications Interface Module
and verifies it is scanning for gauges. If the 8203 Dual RS-485 Communications
Interface Module fails, the 0x0010 and the 0x0001 bits of the PntStatus will be
set to indicate the failure.
Dynamic Parameters
Function
Command
The Command parameter allows you to issue a single command to the gauge.
Valid commands include:
Cancel
Clear Mods
Restart
Save to EEPROM
Calibrate
Enc Battery Off
LevelRef
Calibration Level. The LevelRef provides a means to calibrate the level in the
tank gauge transmitter. Set the LevelRef and then issue a Calibrate command.
Mass
Floating point value representing the Effective Mass (32 bit Register 0025).
NetMass
Floating point value representing the True Mass (32 bit Register 0026).
Density
Floating point value representing the Density (32 bit Register 0027).
CorrDensity
Floating point value representing the Standard Density (32 bit Register 0028).
Reserved
Reserved
Level
Floating point value representing the Tank Level (32 bit Register 0030).
WaterLevel
Floating point value representing the Water Level (32 bit Register 0031).
GrossVolume
Floating point value representing the Product Volume (32 bit Register 0032).
NetVolume
Floating point value representing the Standard Product Volume (32 bit Register
0033).
WaterVolume
Floating point value representing the Water Volume (32 bit Register 0034).
Ullage
Floating point value representing the Remaining Volume (32 bit Register 0035).
Temp
Floating point value representing the Product Temperature (32 bit Register
0036).
AmbientTemp
Floating point value representing the Ambient Temperature (32 bit Register
0037).
Tb
Floating point value representing the Bottom Temperature (32 bit Register
0038)
Tm
Floating point value representing the Middle Temperature (32 bit Register 0039)
Tt
Floating point value representing the Top Temperature (32 bit Register 0040)
TimeToFill
Floating point value representing the Time to Fill (32 bit Register 0041)
FlowRate
Floating point value representing the Flow Rate (32 bit Register 0042)
RoofMass
Floating point value representing the Roof Mass (32 bit Register 0043)
HeadPress
Floating point value representing the Head Pressure (32 bit Register 0044)
Pb
Floating point value representing the Bottom Pressure (32 bit Register 0045)
Pm
Floating point value representing the Middle Pressure (32 bit Register 0046)
AvlInventory
Floating point value representing the Available Inventory (32 bit Register 0047)
Configuration Parame-
ters
Function
Содержание 8300 series
Страница 2: ......
Страница 6: ...Tank Gate Interface iv Installation and Operations Manual ...
Страница 14: ...Overview Tank Gate Interface 4 Installation and Operations Manual ...
Страница 50: ...Software Description Tank Gate Interface 40 Installation and Operations Manual ...
Страница 52: ...Dual RS 485 MODBUS Software Blocks Tank Gate Interface 42 Installation and Operations Manual ...
Страница 56: ...Tank Gate Interface 46 Installation and Operations Manual ...
Страница 68: ...Tank Gate Interface 58 Installation and Operations Manual ...
Страница 100: ...Tank Gate Interface 90 Installation and Operations Manual ...
Страница 108: ...Dual RS 485 GSI ASCII Software Blocks Tank Gate Interface 98 Installation and Operations Manual ...
Страница 112: ...Tank Gate Interface 102 Installation and Operations Manual ...
Страница 115: ...8303 Installation Varec Inc 105 s Figure 7 2 Tank Gate Interface Dimensions 197 204 125 ...
Страница 148: ...Appendix Order Codes Tank Gate Interface 138 Installation and Operations Manual ...
Страница 149: ......