IRM-5000P USER’S MANUAL
49
4.2
Setting the Frequency
To set the frequency:
a.
Start from the “START-UP” menu:
Press the
[2]
key (
UTILITIES
).
b.
The following screen will be displayed:
Press the
[3]
key (
SETUP
).
c.
The following screen will be displayed:
Press the
[4]
key (
50/60Hz
).
d.
The following screen will be displayed:
Press the
[1]
key (
60 Hz
) to set the frequency to 60 Hz, or press the
[2]
key (
50 Hz
). The
setting will be stored and you will be returned to the “START-UP” menu.
1.TEST ID 2.CLOCK
3.COMP INT 4.50/60Hz
5.
°
C/
°
F
TERMINAL VTG: 1 V
1. 60 Hz
2. 50 Hz
TERMINAL VTG: 1 V
1.PRINT 2.SAVE/RES
3.SETUP
TERMINAL VTG: 1 V
3.
RUN TEST 05/05/10
4.
UTILITIES 15:15:15
Bat:
TERMINAL VTG: 1 V