REV 2
IRM-5000P USER’S MANUAL
17
f.
The following screen will be displayed:
1.
YES
Press the
[1]
key (
YES
) to print the resistance readings on the IRM-5000P’s built-
in thermal printer. If this option is selected, the resistance values will be printed
at every second, starting at 10 seconds.
Continue to step g
.
2.
NO
Press the
[2]
key (
NO
) if you do not want to print the resistance readings.
Continue to step g
.
g.
The following screen will be displayed if the IRM-5000P needs to perform self-
calibration:
The remaining calibration time is displayed in seconds. When the calibration is
completed, the following screen will be displayed:
Press the
[ENTER]
key to start the test.
h.
The following screen will be displayed while the test is being performed:
NOTE
The resistance value symbols are:
T = Tera-ohm
G = Giga-ohm
M = Mega-ohm
K = Kilo-ohm
Bat:
Time: 09:51
Resistance: 983.8 M
Current: 47 uA
TEST VOLTAGE: 4999V
“ENTER” TO START!
R 5000V 10Min
TERMINAL VTG: 1 V
CALIBRATING
PLEASE WAIT 25
TERMINAL VTG: 1 V
PRINT DURING TEST?
1. YES 2. NO
TERMINAL VTG: 1 V
Содержание IRM-5000P
Страница 25: ...REV 2 IRM 5000P USER S MANUAL 21 Figure 6 Current Plot from a Resistance Test...
Страница 36: ...IRM 5000P USER S MANUAL REV 2 32 Figure 10 Step Voltage Test Results Report Printout...
Страница 37: ...REV 2 IRM 5000P USER S MANUAL 33 Figure 11 Step Voltage Test Resistance and Current Plots...
Страница 42: ...IRM 5000P USER S MANUAL REV 2 38 Figure 13 Dielectric Discharge Test Resistance Plot...
Страница 43: ...REV 2 IRM 5000P USER S MANUAL 39 Figure 14 Dielectric Discharge Test Current Plot...
Страница 49: ...REV 2 IRM 5000P USER S MANUAL 45 Figure 15 Typical Test Record Directory Printout...