E5 Series High Performance Universal Inverter User’s Manual
86
Chapter 6 Parameter Descriptions
6.8 Multi-Function Output Parameters (Group P7)
YT, relay terminals: multi-function digital output.
YTTDO: multi-function digital output or high-speed pulse output (0 ~ 50kHz).
AOT and AOT: multi-function analog output. 0 ~ T0V or 0 ~ T0mA can be selected by jumper.
The definition table of multi-function digital signal output is as follows:
Setting
Function
Setting
Function
0
Signal indicating that the inverter is running (RUN)
T
Running frequency arrival output(FAR)
T
Frequency level detection T output(FDTT)
3
Frequency level detection T output (FDTT)
4
Inverter or motor overload pre−alarm(OL)
5
Under voltage (LU)
6
Stop due to external fault input (EXT)
7
Frequency reach upper limit(FHL)
8
Frequency reach lower limit(FLL)
9
Frequency reach 0 Hz (still output at stop status)
T0
Preset counting value reached
TT
Designated counting value reached
TT
Reserved
T3
Ready for operation (RDY)
T4
Fault output
T5
Alarm output (only alarm but not stop)
T6
Reserved
T7
Accumulative running time reached
T8
Continuous running time reached
T9
Output XT
T0
Output XT
TT
Reserved
TT
Zero current detection arrival (relative to motor)
T3
Stop command (still output in stop status)
T4
Run command direction instruction
T5
Running status direction instruction
3T
Sleep status indication
T6~3T, 33~47: Reserved
00: Signal indicating that the inverter is running (RUN)
The signal is enabled when the inverter is running.
0T: Running frequency arrival output (FAR)
When the deviation between the output frequency and the reference frequency is in the range of
P7.T9 (running frequency arrival detection level), the signal is enabled. Refer to P7.T9 for details.
0T: Frequency level detection T output (FDTT)
When the output frequency is higher than P7.T0 setting, the signal is enabled. When the output
frequency is less than P7.TT setting, the signal is disabled. Refer to P7.T0 ~ P7.TT for details.
03: Frequency level detection T output (FDTT)
When the output frequency is higher than P7.TT setting, the signal is enabled. When the output
frequency is less than P7.T3 setting, the signal is disabled. Refer to P7.TT ~ P7.T3 for details.
48 ~ 7T(49)
AOT output function selection
P7.04
48 ~ 7T(48)
AOT output function selection
P7.03
00 ~ 47(T4)
Relay output function selection
P7.0T
00 ~ 7T(0T)
YTTDO output function selection
P7.0T
00 ~ 47(00)
YT output function selection
P7.00
Содержание E5 Series
Страница 1: ...E5 Series High Performance Universal Inverter USER S MANUAL E5 Series USER S MANUAL ...
Страница 7: ...vi T Setting Process for Open Loop ...
Страница 8: ...vii Open loop setting process continued ...
Страница 9: ...viii 3 Setting Process for Closed Loop ...
Страница 10: ...ix Setting Process for Closed Loop continued ...
Страница 11: ...x 4 Setting Process for Composite Control ...