E5 Series High Performance Universal Inverter User’s Manual
84
Chapter 6 Parameter Descriptions
Curve 3 have a linear correspondence and curve 4 have four-point correspondence.
The input analog characteristics curve as shown in the following figure. Curve 4 is described as an
example here.
Curves 3 and 4 convert the externally input analog into the internal value. All the AI and DI inputs will be
converted to percentage. The maximum analog input or maximum pulse frequency input corresponding
T00.0% per unit value.
The function of per unit value is determined by the analog channel function selection P6.TT.
Figure 6−T4 Input analog characteristics curve
P6.TT is used to select functions of AIT, AIT, AI3 and DI input. The using methods of AIT, AIT, AI3 and DI
are identical.
P6.TT AIT~AI3
、
DI analog channel function selection
Ones place
AIT function selection
0
:
Open loop frequency, close loop reference, close loop feedback
T~4
:
Reserved
5
:
Motor temperature feedback (overload protection sensor mode)
6
:
Reserved
Tens place
AIT function selection, same as above
Hundreds place
AI3 function selection, same as above
Thousands place
DI function selection, same as above
0: Open loop frequency reference, analog close loop reference, close loop feedback.
For open loop frequency reference, refer to the parameter description of P0.04.
For analog close loop reference, refer to the parameter description of PT.0T, PT.03.
For analog close loop feedback, refer to the parameter description of PT.05, PT.06.
5: Motor temperature feedback: It is used together with parameter P9.T7 for motorthermal protection.
T to 4, 6: Reserved
Note:
If the analog channel function is set a non−zero value, please make sure that different analog channels
have different functions.
0000 ~ 6666(0000)
AIT
~
AI3
、
DI analog channel function selection
P6.TT
Содержание E5 Series
Страница 1: ...E5 Series High Performance Universal Inverter USER S MANUAL E5 Series USER S MANUAL ...
Страница 7: ...vi T Setting Process for Open Loop ...
Страница 8: ...vii Open loop setting process continued ...
Страница 9: ...viii 3 Setting Process for Closed Loop ...
Страница 10: ...ix Setting Process for Closed Loop continued ...
Страница 11: ...x 4 Setting Process for Composite Control ...