E5 Series High Performance Universal Inverter User’s Manual
Chapter 6 Parameter Descriptions
113
6.T5 Fault Record Parameters (Group d0)
The inverter can record the latest three fault code serial number (see 7.T list of fault and alarm
information) and bus voltage, output current and running frequency when fault recently occurred.
Note:
Under−voltage display (LU), the parameters of fault type and fault data will not be saved.
The inverter automatically record the following information: Accumulative power−on time, accumulative
operation time, heat
−
sink maximum temperature record, bus voltage maximum fluctuation, etc.
When the inverter trip by over current, over voltage, short circuited to ground, output phase imbalance,
etc. There may be occur E.FAL fault, D0.TT is used to displayed the E.FAL fault type:
0: None
T: Module protection
T: Over current
3: Over voltage
4: Short circuited to ground
5: Vagueness state, interfere and all of above are possible
0 ~ 5(0)
E.FAL protection type
d0.TT
0.00 ~ 300.00Hz (0.00Hz)
Reserved
d0.T0
0 ~ T000V (0V)
Bus voltage maximum fluctuation record
d0.09
0.0 ~ T00.0
º
C (0.0
º
C)
Heat-sink maximum temperature record
d0.08
0.000 ~ 65.535 kh (0.000kh)
Accumulative running time
d0.07
0.000 ~ 65.535 kh (0.000kh)
Accumulative power
−
on time
d0.06
0.00 ~ 300.00 Hz (0.00Hz)
Frequency of latest fault
d0.05
0.0 ~ 6553.5 A (0.0A)
Current of latest fault
d0.04
0 ~ 65535 V (0V)
Bus voltage of latest fault
d0.03
0 ~ 6T(0)
Fault record 0 (Latest)
d0.0T
0 ~ 6T(0)
Fault record T
d0.0T
0 ~ 6T(0)
Fault record T
d0.00
Содержание E5 Series
Страница 1: ...E5 Series High Performance Universal Inverter USER S MANUAL E5 Series USER S MANUAL ...
Страница 7: ...vi T Setting Process for Open Loop ...
Страница 8: ...vii Open loop setting process continued ...
Страница 9: ...viii 3 Setting Process for Closed Loop ...
Страница 10: ...ix Setting Process for Closed Loop continued ...
Страница 11: ...x 4 Setting Process for Composite Control ...