Technical description
2 Protection functions
2.13 Inverse time operation
VM265.EN011
VAMP 24h support phone +358 (0)20 753 3264
93
Example for Delay type RI :
k
= 0.50
I
= 4 pu
I
pickup
= 2 pu
3
.
2
2
4
236
.
0
339
.
0
5
.
0
RI
t
The operation time in this example will be 2.3 seconds. The
same result can be read from Figure 2.13.1-15.
Example for Delay type RXIDG:
k
= 0.50
I
= 4 pu
I
pickup
= 2 pu
9
.
3
2
5
.
0
4
ln
35
.
1
8
.
5
RXIDG
t
The operation time in this example will be 3.9 seconds. The
same result can be read from Figure 2.13.1-16.
Figure 2.13.1-15 Inverse delay of
type RI.
Figure 2.13.1-16 Inverse delay of
type RXIDG.