Operation and configuration
instructions
2 Local panel user interface
2.4 Configuration and parameter
setting
VM265.EN011
VAMP 24h support phone +358 (0)20 753 3264
33
TRANSFORMER SETTING
Rated voltage in IL side (typically high voltage side)
Rated voltage in I’L side (typically low voltage side)
Rated power of transformer
Connection group of transformer
Zero current compensation in IL side (If transformer is
earthed in IL side, this must set as “ON”)
Zero current compensation in I’L side (If transformer is
earthed in I’L side, this must set as “ON”)
Connection group of the unit transformer, if any. IEC
marking with capital letters Y and D for HV side and small
case letters y and d for LV side combined with the dial hour
is used. For example Yd11 means a wye-delta transformer
where the delta side phase-to-ground voltages are leading
30
the wye side phase-to-ground voltages.
DEVICE INFO
Relay type (Type VAMP 265)
Serial number (SerN)
Software version (PrgVer)
Bootcode version (BootVer)
DATE/TIME SETUP
Day, month and year (Date)
Time of day (Time)
Date format (Style). The choices are "yyyy-mm-dd",
"dd.nn.yyyy" and "mm/dd/yyyy".
CLOCK SYNCHRONISATION
Digital input for minute sync pulse (SyncDI). If any digital
input is not used for synchronization, select "
".
Daylight saving time for NTP synchronization (DST).
Detected source of synchronization (SyScr).
Synchronization message counter (MsgCnt).
Latest synchronization deviation (Dev).
The following parameters are visible only when the access level
is higher than "User".
Offset, i.e. constant error, of the synchronization source
(SyOS).
Auto adjust interval (AAIntv).
Average drift direction (AvDrft): "Lead" or "lag".
Average synchronization deviation (FilDev).