5.7 Logic functions
5 Control functions
Technical description
134
VAMP 24h support phone +358 (0)20 753 3264
VM265.EN011
5.6.1.
Local/Remote selection
In Local mode, the output relays can be controlled via a local
HMI, but they cannot be controlled via a remote serial
communication interface.
In Remote mode, the output relays cannot be controlled via a
local HMI, but they can be controlled via a remote serial
communication interface.
The selection of the Local/Remote mode is done by using a local
HMI, or via one selectable digital input. The digital input is
normally used to change a whole station to a local or remote
mode. The selection of the L/R digital input is done in the
“Objects” menu of the VAMPSET software.
NOTE! A password is not required for a remote control operation.
5.7.
Logic functions
The relay supports customer-defined programmable logic for
boolean signals. The logic is designed by using the VAMPSET
setting tool and downloaded to the relay. Functions available
are:
AND
OR
XOR
NOT
COUNTERs
RS & D flip-flops
Maximum number of outputs is 20. Maximum number of input
gates is 31. An input gate can include any number of inputs.
For detailed information, please refer to the VAMPSET manual
(VMV.EN0xx).