2.13 Inverse time operation
2 Protection functions
Technical description
92
VAMP 24h support phone +358 (0)20 753 3264
VM265.EN011
Figure 2.13.1-13 IEEE2 very inverse
delay
Figure 2.13.1-14 IEEE2 extremely
inverse delay
RI and RXIDG type inverse time operation
These two inverse delay types have their origin in old ASEA
(nowadays ABB) earth fault relays.
The operation delay of types RI and RXIDG depends on the
measured value and other parameters according Equation
2.13.1-3 and Equation 2.13.1-4. Actually these equations can
only be used to draw graphs or when the measured value I is
constant during the fault. Modified versions are implemented
in the relay for real time usage.
Equation 2.13.1-3. RI
pickup
RI
I
I
k
t
236
.
0
339
.
0
Equation 2.13.1-4 RXIDG
pickup
RXIDG
I
k
I
t
ln
35
.
1
8
.
5
t
= Operation delay in seconds
k
= User‟s multiplier
I
= Measured value
I
pickup
= User‟s pick up setting