2.13 Inverse time operation
2 Protection functions
Technical description
86
VAMP 24h support phone +358 (0)20 753 3264
VM265.EN011
The operation time in this example will be 5 seconds. The same
result can be read from Figure 2.13.1-1 .
Figure 2.13.1-1 IEC normal inverse
delay.
Figure 2.13.1-2 IEC extremely inverse
delay.
Figure 2.13.1-3 IEC very inverse
delay.
Figure 2.13.1-4 IEC long time inverse
delay.