9.4 Supporting functions
9 Technical data
Technical description
212
VAMP 24h support phone +358 (0)20 753 3264
VM265.EN011
9.4.
Supporting functions
9.4.1.
Disturbance recorder (DR)
The operation of disturbance recorder depends on the following settings. The
recording time and the number of records depend on the time setting and
the number of selected channels.
Disturbance recorder (DR)
Mode of recording:
Saturated / Overflow
Sample rate:
- Waveform recording
- Trend curve recording
32/cycle, 16/cycle, 8/cycle
10, 20, 200 ms
1, 5, 10, 15, 30 s
1 min
Recording time (one record)
0.1 s – 12 000 min
(must be shorter than MAX time)
Pre-trigger rate
0 – 100%
Number of selected channels
0 – 12
Содержание 265
Страница 2: ...VM265 EN011...
Страница 214: ...11 Construction Technical description 214 VAMP 24h support phone 358 0 20 753 3264 VM265 EN011 11 Construction...