USER'S GUIDE____________________________________________________________________
116 _________________________________________________________________ M210762EN-D
Setting Relay Outputs
NOTE
When having only one relay module installed, its relays are called 'relay
1' and 'relay 2'.
When having two relay modules, the relays of the module connected to
slot
MODULE 1 (communications)
are called 'relay 1' and 'relay 2'
and relays connected to slot
MODULE 2
are called 'relay 3' and 'relay
4'
0706-029
Figure 62
Relay Availability
Arrow in Figure 62 above shows where enabled relays are listed on the
display. Activation state shown in black. Disabled relays are not shown.
Use the display/keypad to set the relay outputs.
1. Open
the
MAIN MENU
by pressing any of the
▲▼◄►
arrow
buttons.
2. Select
Interfaces
, confirm by pressing the
►
arrow button.
3. Select
Relay outputs
, confirm by pressing the
►
arrow button.
4. Select
Relay 1/2/3/4
, confirm by pressing the
►
arrow button.
5. Select
the
Quantity
, confirm by pressing
Change
. Select the
Quantity by using the arrow buttons. Confirm your selection by
pressing
Select
. (Press
Fault Status
when the relay follows the
transmitter error.) Press
Change
to set the value.
6. Select
Act. above / Act
. below. Press
SET
to confirm your
selection. If asked, select
MODIFY
if you want to set the setpoint
by using the arrow buttons. Select
REMOVE
if you want to
remove the setpoint.
7. Select
Hysteresis
. Press
SET
. Set the hysteresis by using the arrow
buttons. Press
OK
.
8. Select
Relay enable
, press
ON/OFF
to enable/disable the relay.