Installation manual remote control device VR 90 0020055329_00
26
Display
Meaning / Explanation
Fault message
Phone No:
Fault Number
Fault code
> 1
1
19.07.02 16:55
VR 60 address 3
Not achievable
There is no communication with the VR 60 mixer module with the set bus address. The
affected components as well as the inaccessible address are always displayed first in this
error message, along with the information that communication has been interrupted.
The cause for this can be, for example, that the bus cable is not connected, or that the
voltage supply is not available, or else that the components are defective.
Fault message
Phone No:
Fault Number
Fault code
> 1
1
19.07.02 16:55
VRC 630
Not achievable
Base controller not accessible.
Fault message
Phone No:
Fault Number
Fault code
> 1
7
19.07.02 16:55
heat zone 1 is not configured as
a heat zone
Incorrect configuration of the heating circuit.
Table 6.1 List of error codes
6 Error codes