Installation manual remote control device VR 90 0020055329_00
20
4.2 Setting
Bus
address
Communication within the system takes place via eBus. In
order to ensure perfect communication between all
components it is necessary to provide the remote control
device with an address which matches the heating circuit
to be controlled.
Correct addressing for the individual system components
can be seen in Table 4.1.
4
4.2 Setting Bus address
System components
Address of the
components
Bus address to be
set in the VR 90
Heating circuit 1
VRC 630
1
Heating circuit 2
VRC 630
2
Heating circuit 3
VRC 630
3
VR 60, Address 4
HC 4
HC 5
4
5
VR 60, Address 6
HC 6
HC 7
6
7
VR 60, Address 8
HC 8
8
Table 4.1 Bus addresses to be set
4 Electrical installation