Technical data
Installation and maintenance instructions ecoTEC plus 0020134833_01
85
17
17
Technical data
ecoTEC plus
Unit
937 (VUI GB 376/5-5)
Nominal heat output range P at 50/30 °C
kW
7.1 - 30.1
Nominal heat output range P at 80/60 °C
kW
6.4 - 28.6
Maximum heat output for hot water generation
kW
38.7
Maximum heat input for hot water generation
kW
39.2
Maximum heat input at the heating side
kW
28.9
Minimum heat input G20
kW
6.8
Minimum heat input G31
kW
9.0
Minimum heat output for G31
kW
8.5
Heating output setting range
kW
6 - 28
Heating
Max. flow temperature
°C
85
Max. flow temperature setting range
(factory setting: 75 °C)
°C
30 - 80
Min. pressure for full operation
MPa/bar
0.8
Permissible total overpressure
MPa/bar
0.3/3
Expansion vessel capacity
l
10
Circulation water quantity (with reference to
D
T = 20 K)
l/h
1204
Condensate rate approx. (pH value 3.5 °–4.0)
in heating mode 50 °C flow/30 °C return
l/h
2.9
Remaining feed head of pump (at nominal circulation
water volume)
MPa/bar
0.020/0.20
Hot water handling
Lowest water volume
l/min
1.5
Water volume (at
D
T = 42 K)
l/min
13.2
Water volume (at
D
T = 35 K)
l/min
15.8
Water volume (at
D
T = 30 K)
l/min
18.5
Permitted overpressure
MPa/bar
1.0/10
Required connection pressure
MPa/bar
0.035/0.35
Hot water output temperature range
°C
35 - 65
General
Boiler-side gas connection
mm
22
Flow/return heating connections, boiler side
mm
22
Connecting the hot and cold water, boiler side
Inches
G 3/4
Connector expansion relief valve (minimum)
mm
15
Condensate discharge pipework (minimum)
mm
19
Flue gas spigot
mm
60/100 (concentric), optional 80/125 (concentric)
Gas connection pressure (gas flow pressure) natural
gas, G20
kPa/mbar
0.20/20
Gas connection pressure (gas flow pressure) propane,
G31
kPa/mbar
0.37/37
Gas flow rate at 15 °C and 1013 mbar
(based on hot water generation if applicable)
G20
G31
m
3
/h
kg/h
4.1
3.05
Flue gas mass rate min./max.
g/s
3.0/17.6
Flue gas temperature min./max.
°C
40/70
Approved flue gas connections
C13, C33, C43, C53, C83, C93, B53P
NOx class
5
NOx
mg/kWh
27.4
SEDBUK (2005)
A
SEDBUK (2009) (G20)
89.4
Boiler dimensions (H x W x D)
mm
720 x 440 x 601
Mounting weight approx.
kg
41
Electrical connection
V/Hz
230/50
Built-in fuse
2 A, slow-blow
17.1
Technical data for ecoTEC plus VUI boiler