70
Alarm
Description
No flow
If for any reason there is no flow through the Oilcon
®
Oil Discharge Monitoring and Control
System the NO FLOW alarm is activated. The Sample pump will be stopped automatically to
prevent any damage to the pump or motor.
If in flush or shutdown mode the system will return to standby mode. When in Sample mode the
system will go to the Idle mode.
Zero error
During the calibration check of the Oilcon
®
Oil Discharge Monitoring and Control System, during
Flush or Manual Flush mode, the ZERO ERROR alarm can be activated if the flushing water is
dirty, oily or if it contains air.
The system will go to Idle mode and from there only the Shutdown mode can be selected, to
resume operation after the fault is cleared. Thus a restart is made from Standby.
Path dirty
During the calibration check of the Oilcon
®
Oil Discharge Monitoring and Control System the
PATH DIRTY alarm can be activated if the optical path between the laser transmitter and the
direct receiver is obscured.
The system will go to Idle mode and from there only the Shutdown mode can be selected, to
resume operation after the fault is cleared. Thus a restart is made from Standby.
Power/communication
failure
If during operation of the Oilcon
®
Oil Discharge Monitoring and Control System a fault develops in
the communication link between the MCU and the EPU or a power failure condition occurs, then
the POWER/COMMUNICATION FAILURE alarm is activated.
The system will go to the Standby mode. However during such a situation the emergency power
supply will take over, thus no data will be lost.
Led monitor error
If an optical LED failure is detected during operation of the Oilcon
®
Oil Discharge Monitoring and
Control System the LED MONITOR ERROR alarm is activated.
Flow overrange
Flowmeter 1 or 2
If during operation of the Oilcon
®
Oil Discharge Monitoring and Control System an over-range
fault is detected in the flowmeter signal the FLOW OVERRANGE alarm is activated. The specific
flowmeter-1 or -2 is shown.
Flow underrange
Flowmeter 1 or 2
If during operation of the Oilcon
®
Oil Discharge Monitoring and Control System an under-range
fault is detected in the flowmeter signal the FLOW UNDERRANGE alarm is activated. The
specific flowmeter-1 or -2 is shown.
This alarm is only applicable if the Oilcon
®
Oil Discharge Monitoring and Control System is
equipped with two flowmeters.
In case an alarm is triggered, section 15 of this manual should be consulted for corrective actions.
7.6 SYSTEM
FAILURES
IMPORTANT:
On any failure of the system the discharge should be stopped and the failure should be
noted in the Oil Records Book. A manually operated alternative system shall be
provided and may be used in the event of such a failure, but the defective unit must be
made operable before the tanker commences its next ballast voyage, unless it is
proceeding to a repair yard.
7.6.1 Auto/manual
operation
In the occasion of a failure of one of the three transducers in the system (Oilcon
®
Oil Discharge
Monitoring and Control System, ships log or discharge flowmeter) the input of these transducers can
be changed from Auto to Manual. This can be done by following the next instructions:
1. operate the MCU until the system is in SET Up mode or the IDLE SET UP mode.
2. select the appropriate input (ship’s speed, discharge flowrate or oil content).
3. change the appropriate input from automatic to manual or vice versa: Automatic input is
indicated by “A”, manual input by “M”.
4. enter the value for that input with the numeric keys.
5. operate the system until back in IDLE mode.
Содержание OILCON MARK 6M
Страница 112: ...111...
Страница 113: ...112...
Страница 114: ...113...
Страница 115: ...114...
Страница 116: ...115...
Страница 117: ...116...
Страница 118: ...117...
Страница 119: ...118...
Страница 120: ...119...
Страница 121: ...120...
Страница 122: ...121...
Страница 123: ...122...
Страница 124: ...123...
Страница 125: ...124...
Страница 128: ...127 Drawing 1 0806 0005 Sheet 1 2...
Страница 129: ...128 Drawing 2 0806 0005 Sheet 2 2...
Страница 130: ...129 Drawing 3 0806 1041...
Страница 131: ...130 Drawing 4 0806 1075...
Страница 132: ...131 Drawing 5 0806 1076...
Страница 133: ...132 Drawing 6 0806 1077...
Страница 134: ...133 Drawing 7 0806 1260 Sheet 1 2...
Страница 135: ...134 Drawing 8 0806 1260 Sheet 2 2...
Страница 136: ...135 Drawing 9 0806 1265...
Страница 137: ...136 Drawing 10 0806 1267...
Страница 138: ...137 Drawing 11 0806 1268...
Страница 139: ...138 Drawing 12 0806 1279...
Страница 140: ...139 Drawing 13 0806 1285...
Страница 141: ...140 Drawing 14 0806 1286...
Страница 142: ...141 Drawing 15 0806 1287...
Страница 143: ...142 Drawing 16 0806 1288...
Страница 144: ...143 Drawing 17 0806 1621...
Страница 145: ...144 Drawing 18 0806 1622...
Страница 146: ...145 Drawing 19 0806 2032...
Страница 147: ...146 Drawing 20 0806 2048...
Страница 148: ...147 Drawing 21 0806 2050...
Страница 149: ...148 Drawing 22 0806 5019...
Страница 150: ...149 Drawing 23 0806 5026...
Страница 151: ...150 Drawing 24 0806 8016...
Страница 152: ...151 Drawing 25 0806 8023...
Страница 153: ...152 Drawing 26 0806 8035...
Страница 154: ...153 Drawing 27 0806 8038 Sheet 1 4...
Страница 155: ...154 Drawing 28 0806 8038 Sheet 2 4...
Страница 156: ...155 Drawing 29 0806 8038 Sheet 3 4...
Страница 157: ...156 Drawing 30 0806 8038 Sheet 4 4...
Страница 158: ...157 Drawing 31 0806 8039...
Страница 159: ...158 Drawing 32 0806 8040...
Страница 160: ...159 Drawing 33 0806 8070...
Страница 161: ...160 Drawing 34 0810 2010...
Страница 162: ...161 Drawing 35 0871 1213...
Страница 163: ...162 Drawing 36 0899 1092...
Страница 164: ...163 Drawing 37 0899 1163...
Страница 165: ...164 Drawing 38 0899 1249...
Страница 166: ...165 Drawing 39 0899 1256...
Страница 167: ...166 Drawing 40 0899 1258...
Страница 168: ...167 Drawing 41 0899 1259...