CONTROL KEYPAD
vacon • 93
9.3.7
Expander board menu (M7)
The
Expander board menu
makes it possible for the user 1) to see what expander boards are
connected to the control board and 2) to reach and edit the parameters associated with the expander
board.
Enter the following menu level (G#) with the
. At this level, you can browse
through slots (see page 56) A to E with the
to see what expander boards are
connected. On the lowermost line of the display you also see the number of parameters associated
with the board. You can view and edit the parameter values in the same way as described in chapter
9.3.2. See Table 9-11 and Figure 9-27.
Expander board parameters
Code
Parameter
Min
Max
Default
Cust
Selections
P7.1.1.1
AI1
mode
1
5
3
1=0…20 mA
2=4…20 mA
3=0…10 V
4=2…10 V
5=–10…+10 V
P7.1.1.2
AI2 mode
1
5
1
See P7.1.1.1
P7.1.1.3
AO1
mode
1
4
1
1=0…20 mA
2=4…20 mA
3=0…10 V
4=2…10 V
Table 9-11. Expander board parameters (board OPT-A1)
Figure 9-27. Expander board information menu
9.4 Further keypad functions
The Vacon NX control keypad embodies additional application-related functions. See Vacon NX
Application Package for more information.
G1
G5
READY
READY
G1
G2
RE ADY
READY
enter
P1
P4
R EA DY
I/Oterm
G1
G2
R EA DY
I/Oterm
V1
V2
READY
R EA DY
I/Oterm
D:NXOPTC2
C:NXOPTC1
Expander boards
Parameters
Slave address
126
Slave address
126
Baud rate
Auto
Monitor
C H AN GE VA LUE
C ON FIR M CHA NGE