16 • vacon
TECHNICAL DATA
4.1.3
Vacon NXP/C 6 – Mains voltage 500—690 V
High overload = Max current IS, 2 sec/20 sec, Rated overload current, 1 min/10 min
Following continuous operation at rated output current, rated overload current
for 1 min, followed by a period of load current less than rated current, and of
such duration that the r.m.s output current, over the duty cycle, does not exceed
rated output current (IH)
Low overload = Max current IS, 2 sec/20 sec, Rated overload current, 1 min/10 min
Following continuous operation at rated output current, rated overload current
for 1 min, followed by a period of load current less than rated current, and of
such duration that the r.m.s output current, over the duty cycle, does not exceed
rated output current (IL)
Mains voltage 500-690 V, 50/60 Hz, 3~
Frequency
converter
type
Loadability
Motor shaft power
Frame
Dimensions and
weight*
WxHxD/kg
Low
High
690V supply
575V supply
Rated
contin.
current I
L
(A)
Rated
overload
current
(A)
Rated
contin.
current I
H
(A)
50%
overload
current
(A)
Max
current
I
S
Low
overload
P(kW)
High
overload
P(kW)
Low
overload
P(hp)
High
overload
P(hp)
NX_0125 6
125
138
100
150
200
110
90
125
100
FR9
606x2275x605/371
NX_0144 6
144
158
125
188
213
132
110
150
125
FR9
606x2275x605/371
NX_0170 6
170
187
144
216
245
160
132
150
150
FR9
606x2275x605/371
NX_0208 6
208
229
170
255
289
200
160
200
150
FR9
606x2275x605/371
NX_0261 6
261
287
208
312
375
250
200
250
200
FR10
606x2275x605/341
NX_0325 6
325
358
261
392
470
315
250
300
250
FR10
606x2275x605/371
NX_0385 6
385
424
325
488
585
355
315
400
300
FR10
606x2275x605/371
NX_0416 6
416**
416**
325
488
585
400**
315
450**
300
FR10
606x2275x605/403
NX_0460 6
460
506
385
578
693
450
355
450
400
FR11
806x2275x605/524
NX_0502 6
502
552
460
690
828
500
450
500
450
FR11
806x2275x605/524
NX_0590 6
590**
649**
502**
753**
904**
560**
500**
600**
500**
FR11
806x2275x605/577
NX_0650 6
650
715
590
885
1062
630
560
650
600
FR12 1206x2275x605/745
NX_0750 6
750
825
650
975
1170
710
630
800
650
FR12 1206x2275x605/745
NX_0820 6
820**
902**
650
975
1170
800**
630
800**
650
FR12 1206x2275x605/745
NX_0920 6
920
1012
820
1230
1410
900
800
900
800
FR13 1406x2275x605/1000
NX_1030 6
1030
1130
920
1380
1755
1000
900
1000
900
FR13 1406x2275x605/1000
NX_1180 6
1180**
1298**
1030**
1463**
1755**
1150**
1000** 1100** 1000**
FR13 1406x2275x605/1000
NX_1500 6
1500
1650
1300
1950
2340
1500
1300
1500
1350
FR14 2406X2275X605/2350
NX_1900 6
1900
2090
1500
2250
2700
1800
1500
2000
1500
FR14 2806X2275X605/2440
NX_2250 6
2250
2475
1900
2782
3335
2000
1800
2300
2000
FR14 2806X2275X605/2500
Table 4-3. Power ratings and dimensions of Vacon NX 6- and 12-pulse drives, supply voltage 500—690V.
Note: The rated currents in given ambient temperatures are achieved only when the switching
frequency is equal to or less than the factory default (automatic thermal management).
*The dimensions indicated are for the basic 6-pulse IP21 version of the converter cabinet. Some op-
tions increase the width, height or weight of the cabinet. Check the delivery specific documentation
for more details.
** Maximum ambient tempe35°C
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]