CONTROL KEYPAD
vacon • 87
7
Fault
code
Fault
Possible cause
Correcting measures
30
Safe disable
The input on OPT-AF board has opened
Cancel Safe Disable if this can be done
safely.
31
IGBT temperature
(hardware)
IGBT Inverter Bridge overtemperature
protection has detected too high a short
term overload current
Check loading.
Check motor size.
Make identification run.
32
Fan cooling
Cooling fan of the AC drive does not start,
when ON command is given
Contact the distributor near to you.
34
CAN bus
communication
Sent message not acknowledged.
Ensure that there is another device on
the bus with the same configuration.
35
Application
Problem in application software
Contact your distributor. If you are
application programmer check the
application program.
36
Control unit
NXS Control Unit can not control NXP
Power Unit and vice versa
Change control unit
37
Device changed
(same type)
Option board or control unit changed.
Same type of board or same power rating
of drive.
Reset. Device is ready for use.
Old parameter settings will be used.
38
Device added
(same type)
Option board or drive added.
Reset. Device is ready for use.
Old board settings will be used.
39
Device removed Option board removed.
Reset. Device no longer available.
40
Device
unknown
Unknown option board or drive.
Subcode in T.14:
S1 = Unknown device
S2 = Power1not same type as Power2
Contact the distributor near to you.
41
IGBT temperature IGBT Inverter Bridge overtemperature
protection has detected too high a short
term overload current
Check loading.
Check motor size.
Make identification run.
42
Brake resistor
overtemperature
Brake resistor overtemperature
protection has detected too heavy braking
Set the deceleration time longer.
Use external brake resistor.
43
Encoder fault
Problem detected in encoder signals.
Subcode in T.14:
1 = Encoder 1 channel A is missing
2 = Encoder 1 channel B is missing
3 = Both encoder 1 channels are missing
4 = Encoder reversed
5 = Encoder board missing
Check encoder channel connections.
Check the encoder board.
Check encoder frequency in open loop.
44
Device changed
(different type)
Option board or power unit changed.
New device of different type or different
power rating.
Reset
Set the option board parameters again if
option board was changed.
Set converter parameters again if power
unit was changed.
45
Device added
(different type)
Option board of different type added.
Reset
Set the option board parameters again.
49
Division by zero
in application
Division by zero has occurred in
application program.
Contact your distributor if the fault re-
occurs while the converter is in run
state. If you are application programmer
check the application program.
50
Analogue input
I
in
< 4mA (sel.
signal range 4
to 20 mA)
Current at the analogue input is < 4mA.
control cable is broken or loose
signal source has failed
Check the current loop circuitry.
51
External fault
Digital input fault.
Remove fault situation on external
device.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Содержание NX_ 0003 5
Страница 11: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 12: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 13: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 52: ...52 vacon CABLING AND CONNECTIONS 6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...