CABLING AND CONNECTIONS
vacon • 47
6
6.1.1.6
Cable and fuse sizes, NX_5, FR10 to FR12
The table below shows typical cable sizes and types that can be used with the converter. The final selection
should be made according to local regulations, cable installation conditions and cable specification.
Frame
Type
I
L
[A]
Fuse I
n
[A]
Mains and motor
cable
1)
[mm
2
]
No. of
supply
cables
No. of motor
cables
FR10
NX0385 5
385
400 (3 pcs)
Cu: 2*(3*120+70)
Al: 2*(3*185Al+57Cu)
Even/Odd
Even/Odd
NX0460 5
460
500 (3 pcs)
Cu: 2*(3*150+70)
Al: 2*(3*240Al+72Cu)
Even/Odd
Even/Odd
NX0520 5
520
630 (3 pcs)
Cu: 2*(3*185+95)
Al: 2*(3*300Al+88Cu)
Even/Odd
Even/Odd
FR11
NX0590 5
590
315 (6 pcs)
Cu: 2*(3*240+120)
Al: 4*(3*120Al+41Cu)
Even
Even/Odd
NX0650 5
650
400 (6 pcs)
Cu: 4*(3*95+50)
Al: 4*(3*150Al+41Cu)
Even
Even/Odd
NX0730 5
730
400 (6 pcs)
Cu: 4*(3*120+70)
Al: 4*(3*185Al+57Cu)
Even
Even/Odd
FR12
NX0820 5
820
500 (6 pcs)
Cu: 4*(3*150+70)
Al: 4*(3*185Al+57Cu)
Even
Even
NX0920 5
920
500 (6 pcs)
Cu: 4*(3*150+70)
Al: 4*(3*240Al+72Cu)
Even
Even
NX1030 5
1030
630 (6 pcs)
Cu: 4*(3*185+95)
Al: 4*(3*300Al+88Cu)
Even
Even
Table 6-4. Cable and fuse sizes for Vacon NX_5 (FR10 to FR12)
1)
based on correction factor 0.7
6.1.1.7
Cable and fuse sizes, NX_6, FR10 to FR12
The table below shows typical cable sizes and types that can be used with the converter. The final selection
should be made according to local regulations, cable installation conditions and cable specification.
Frame
Type
I
L
[A]
Fuse I
n
[A]
Mains and motor
cable
1)
[mm
2
]
No of
supply
cables
No of
motor
cables
FR10
NX0261 6 261 315 (3 pcs)
Cu: 3*185+95
Al: 2*(3*95Al+29Cu)
Even/Odd
Even/Odd
NX0325 6 325 400 (3 pcs)
Cu: 2*(3*95+50)
Al: 2*(3*150Al+41Cu)
Even/Odd
Even/Odd
NX0385 6 385 400 (3 pcs)
Cu: 2*(3*120+70)
Al: 2*(3*185Al+57Cu)
Even/Odd
Even/Odd
NX0416 6 416 500 (3 pcs)
Cu: 2*(3*150+70)
Al: 2*(3*185Al+57Cu)
Even/Odd
Even/Odd
FR11
NX0460 6 460 500 (3 pcs)
Cu: 2*(3*150+70)
Al: 2*(3*240Al+72Cu)
Even/Odd
Even/Odd
NX0502 6 502 630 (3 pcs)
Cu: 2*(3*185+95)
Al: 2*(3*300Al+88 Cu)
Even/Odd
Even/Odd
NX0590 6 590 315 (6 pcs)
Cu: 2*(3*240+120)
Al: 4*(3*120Al+41Cu)
Even
Even/Odd
FR12
NX0650 6 650 400 (6 pcs)
Cu: 4*(3*95+50)
Al: 4*(3*150Al+41Cu)
Even
Even
NX0750 6 750 400 (6 pcs)
Cu: 4*(3*120+70)
Al: 4*(3*150Al+41Cu)
Even
Even
NX0820 6 820 500 (6 pcs)
Cu: 4*(3*150+70)
Al: 4*(3*185Al+57Cu)
Even
Even
Table 6-5. Cable and fuse sizes for Vacon NX_6 (FR10 to FR12)
1)
based on correction factor 0.7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Содержание NX_ 0003 5
Страница 11: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 12: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 13: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 52: ...52 vacon CABLING AND CONNECTIONS 6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...