Fault types
In the NX_ AC drive, there are four different types of faults. These types differ from each other on the basis
of the subsequent behaviour of the drive. See Table 7-3.
Figure 7-7. Fault display
Fault type symbol
Meaning
A
(Alarm)
This type of fault is a sign of an unusual operating
condition. It does not cause the drive to stop, nor does it
require any special actions. The 'A fault' remains in the
display for about 30 seconds.
F
(Fault)
An 'F fault' is a kind of fault that makes the drive stop.
Actions need to be taken in order to restart the drive.
AR
(Fault Autoreset)
If an 'AR fault' occurs the drive will also stop
immediately. The fault is reset automatically and the
drive tries to restart the motor. Finally, if the restart is
not successful, a fault trip (FT, see below) occurs.
FT
(Fault Trip)
If the drive is unable to restart the motor after an AR
fault an FT fault occurs. The effect of the 'FT fault' is
basically the same as that of the F fault: the drive is
stopped.
Table 7-3. Fault types
Fault type
symbol
F T1
T13
STOP
FAULT
I/Oterm
STOP
I/Oterm
FAULT
34:21:05
I/O term
17
11 Output phase
Operations days
Operation hours
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Содержание NX_ 0003 5
Страница 11: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 12: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 13: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 52: ...52 vacon CABLING AND CONNECTIONS 6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...