Code
Parameter
Range
Step
Default
Custom
Description
Page
1.1
Minimum frequency
0—120/500 Hz
1 Hz
0 Hz
6
1.2
Maximum frequency
0—120/500 Hz
1 Hz
50 Hz
*)
6
1.3
Acceleration time 1
0.1—3000 s
0.1 s
3 s
Time from f
min
(1.1) to f
max
(1.2)
6
1.4
Deceleration time 1
0.1—3000 s
0.1 s
3 s
Time from f
max
(1.2) to f
min
(1.1)
6
1.5
Reference selection
0—15
1
0
0 = U
in
3 = U
in
– I
in
1 = I
in
4 = I
in
– U
in
2 = U
in
+ I
in
5 = U
in
* I
in
6 = U
in
joystick control
7 = I
in
joystick control
8 = Signal from internal motor pot.
9 = Signal from internal motor pot.
reset if Vacon unit is stopped
6
10 = Signal from internal motor
pot. (stored in menory over
mains break
11= Min (U
in
, I
in
)
12 = Max (U
in
, I
in
)
13 = Panel reference r1
14 = Max reference
15 = U
in
/I
in
selection
1.6
Jogging speed
reference
f
min
– f
max
(1.1) (1.2)
0.1 Hz
5 Hz
7
1.7
Current limit
0.1—2.5 x I
nCX
0.1 A
1.5 x I
cCX
Output current limit [A] of the unit
7
1.8
U/f ratio selection
0—2
1
0
0 = Linear
1 = Squared
2 = Programmable U/f ratio
7
1.9
U/f optimisation
0—1
1
0
0 = None
1 = Automatic torque boost
8
1.10
Nominal voltage of the
motor
180—690
1 V
230 V
400 V
500 V
690 V
Vacon range CX/CXL2
Vacon range CX/CXL/CXS4
Vacon range CX/CXL/CXS5
Vacon range CX6
9
1.11
Nominal frequency of
the motor
30—500 Hz
1 Hz
50 Hz
f
n
on the rating plate of the motor
9
1.12
Nominal speed of the
motor
300—20000 rpm
1 rpm
1440 rpm
n
n
on the rating plate of the motor
9
1.13
Nominal current of the
motor
2.5 x I
nCX
0.1 A
I
nCX
I
n
on the rating plate of the motor
9
180—250
230 V
Vacon range CX/CXL2
380—440
400 V
Vacon range CX/CXL/CXS4
380—500
500 V
Vacon range CX/CXL/CXS5
1.14
Supply voltage
525—690
690 V
Vacon range CX6
9
1.15
Parameter conceal
0—1
1
0
0 = All parameter groups visible
1 = Only group 1 visible
9
1.16
Parameter value lock
0—1
1
0
0 = Parameter changes enabled
1 = parameter changes disabled
9
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
Note!
Note!
Note!
Note!
Note!
STOP
STOP
STOP
STOP
= Parameter value can be changed only when the frequency converter is stopped. (Continues)
Table 5-1. Group 1 basic parameters
5
5
5
5
5
Basic Parameters, Group 1
Basic Parameters, Group 1
Basic Parameters, Group 1
Basic Parameters, Group 1
Basic Parameters, Group 1
5.1
5.1
5.1
5.1
5.1
Parameter table