The Multipurpose Application II has an extra fault code:
8 MONIT
8 MONIT
8 MONIT
8 MONIT
8 MONITORING DA
ORING DA
ORING DA
ORING DA
ORING DAT
T
T
T
TA
A
A
A
A
The Multipurpose Application II has extra items for monitoring (V1 - V24). See table 8-1
Data
Data
Unit
Description
number
name
V1
Output frequency
Hz
Frequency to the motor
V2
Motor speed
rpm
Calculated motor speed
V3
Motor current
A
Measured motor current
V4
Motor torque
%
Calculated actual torque/nominal torque of the unit
V5
Motor power
%
Calculated actual power/nominal power of the unit
V6
Motor voltage
V
Calculated motor voltage
V7
DC-link voltage
V
Measured DC-link voltage
V8
Temperature
°C
Temperature of the heat sink
V9
Operating day counter
DD.dd
Operating days
1)
, not resettable
V10
Operating hours,
HH.hh
Operating hours
2)
, can be reset with
"trip counter"
programmable button #3
V11
MW-hours
MWh
Total MW-hours, not resettable
V12
MW-hours,
MWh
MW-hours, can be reset with programmable
"trip counter"
button #4
V13
Voltage/analogue input
V
Voltage of the terminal U
in
+ (term. #2)
V14
Current/analogue input
mA
Current of terminals I
in
+ and I
in
- (term. #4, #5)
V15
Digital input status, gr. A
V16
Digital input status, gr. B
V17
Digital and relay output
status
V18
Control program
Version number of the control software
V19
Unit nominal power
kW
Shows the power size of the unit
V20
Motor temperature rise
%
100%= temperature of motor has risen to nominal
V21
Reference frequency
Hz
Frequency reference
V22
Torque reference
%
Torque reference when torque control in use
V23
Digital inputs (opt. board)
V24
Fieldbus status
Used with Profibus option board only
Used with Profibus option board only
Used with Profibus option board only
Used with Profibus option board only
Used with Profibus option board only.....
0 = Master-Slave communication not started
1 = Master-Slave communication is starting up
2 = Master-Slave communication started and OK.
1)
DD = full days, dd = decimal part of a day
2)
HH = full hours, hh = decimal part of an hour
Table 8-1 Monitoring items
Fault number
Fault
Possible cause
Checking
27
Fieldbus
communication error
Fieldbus board has detected the reset or
error of the Bus system (physical layer)
Reset the fault and restart
again. If the fault comes
again:
- check the host system
- check the cables