Multi-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application II
Vacon Plc
Phone:
+358-(0)201 2121
Fax: +358-(0)201 212 205
Service:
+358-40-8371 150
E-mail: [email protected]
Group 7, Protections
Group 7, Protections
Group 7, Protections
Group 7, Protections
Group 7, Protections
Code
Parameter
Range
Step
Default
Custom
Description
Page
7
.
.
.
.
.
1
Response to
0—3
1
0
0 = No action
35
reference fault
1 = Warning
2 = Fault, stop according to
par 4.7
3 = Fault, stop always by coasting
7
.
.
.
.
.
2
Response to
0—3
1
2
0 = No action
35
external fault
1 = Warning
2 = Fault, stop according to par 4.7
3 = Fault, stop always by coasting
7
.
.
.
.
.
3
Phase supervision of
0—2
1
2
0 = No action
35
the motor
1 = Warning
2 = Fault
7
.
.
.
.
.
4
Earth fault protection
0—2
1
2
0 = No action
35
1 = Warning
2 = Fault
7
.
.
.
.
.
5
Motor thermal protection
0—2
1
2
0 = No action
36
1 = Warning
2 = Fault
7
.....
6
Motor thermal protection 50.0—150 %
1.0 %
100.0%
36
break point current
x I
nMOTOR
7
.....
7
Motor thermal protection 10.0—150%
1.0 %
45.0%
37
zero frequency current
x I
nMOTOR
7
.....
8
Motor thermal protection
0.5—300.0
0,5
Default value is set according
37
time constant
minutes
min.
to motor nominal current
7
.....
9
Motor thermal protection
10—500 Hz
1 Hz
35 Hz
38
break point frequency
7
.....
10
Stall protection
0—2
1
1
0 = No action
38
1 = Warning
2 = Fault
7
.....
11
Stall current limit
10.0—200%
1.0%
130.0%
39
x I
nMOTOR
7
.....
12
Stall time
2.0—120 s
1.0 s
15.0 s
39
7
.....
13
Maximum stall frequency
1—f
max
1 Hz
25 Hz
39
7
.....
14
Underload protection
0—2
1
0
0 = No action
40
1 = Warning
2 = Fault
7
.....
15
Underload prot., field
20.0—150 %
1.0%
50.0%
40
weakening area load
x T
nMOTOR
7
.....
16
Underload protection, 10.0—150.0% 1.0%
10.0%
40
zero frequency load
x T
nMOTOR
7
.....
17
Underload time
2.0—600.0 s
1.0 s
20.0s
40
7
.
.
.
.
.
18
Phase supervision of
0—2
1
2
0 = No action
41
the supply voltage
1 = Warning
2 = Fault
7
.
.
.
.
.
19
Termistor input of
0—2
1
2
0 = No action
41
I/O-Expander
1 = Warning
2 = Fault
7.20
Response to fieldbus
0
—
2
1
0
0 = Not used
41
fault
1 = Warning
2 = Fault