Multi-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application II
Note!
Note!
Note!
Note!
Note!
= Parameter value can be changed only when the frequency converter is stopped.
(Continues)
Code
Parameter
Range
Step
Default
Description
Page
DIA1
DIA2
2.1
Start/Stop logic
selection
0—4
1
0
0 = Start forw.
1 = Start/Stop
2 = Start/Stop
3 = Start pulse
4 = Start/stop pulse
Start reverse
Reverse
Run enable
Stop pulse
Run enable
19
2.2
DIA3 function
(terminal 10)
0—12
1
7
0 = Not used
1 = External fault, closing contact
2 = External fault, opening contact
3 = Run enable
4 = Accel./decel. time selection
5 = Reverse
6 = Jogging speed
7 = Fault reset
8 = Accel./decel. operation prohibit
9 = DC-braking command
10 = Torque control
11 = Torque reference sign
12 = Run enable with coasting
20
2.3
DIB4 function
(terminal 14)
0—15
1
6
0 = Not used
1 = External fault, closing contact
2 = External fault, opening contact
3 = Run enable
4 = Accel./decel. time selection
5 = Reverse
6 = Jogging speed
7 = Fault reset
8 = Accel./decel. operation prohibit
9 = DC-braking command
10 = Multi-step speed select 1
11 = Selection between I
in
and U
in
12 = Run enable with coasting
13 = Fieldbus control
14 = Par. 1.5 / U
in
15 = Par. 1.5 / I
in
22
2.4
DIB5 function
(terminal 15)
0—13
1
1
0 = Not used
1 = External fault, closing contact
2 = External fault, opening contact
3 = Run enable
4 = Accel./decel. time selection
5 = Reverse
6 = Jogging speed
7 = Fault reset
8 = Accel./decel. operation prohibit
9 = DC-braking command
10 = Multi-step speed select 2
11 = Motorised pot. speed up
12 = Run enable with coasting
13 = Fieldbus control
22
2.5
DIB6 function
(terminal 16)
0—13
1
4
0 = Not used
1 = External fault, closing contact
2 = External fault, opening contact
3 = Run enable
4 = Accel./decel. time selection
5 = Reverse
6 = Jogging speed
7 = Fault reset
8 = Accel./decel. operation prohibit
9 = DC-braking command
10 = Multi-step speed select 3
11 = Motorised pot. speed down
12 = Run enable with coasting
13 = Fieldbus control
22
STO P
STO P
STO P
STO P
STO P
STO P
STO P
STO P
STO P
STO P
STO P
STO P
STO P
STO P
STO P
STO P
STO P
STO P
STO P
STO P
6
6
6
6
6
Special Parameters, Groups 2—10
Special Parameters, Groups 2—10
Special Parameters, Groups 2—10
Special Parameters, Groups 2—10
Special Parameters, Groups 2—10
6.1
6.1
6.1
6.1
6.1
Parameter tables
Parameter tables
Parameter tables
Parameter tables
Parameter tables
Group 2, Input signal parameters
Group 2, Input signal parameters
Group 2, Input signal parameters
Group 2, Input signal parameters
Group 2, Input signal parameters
STOP
STOP
STOP
STOP