background image

Vacon Plc

Phone:

+358-(0)201 2121

Fax: +358-(0)201 212 205

Service:

+358-40-8371 150

E-mail: [email protected]

Page 40

V

V

V

V

Vacon

acon

acon

acon

acon

Multi-purpose Control Application II

Multi-purpose Control Application II

Multi-purpose Control Application II

Multi-purpose Control Application II

Multi-purpose Control Application II

Motor thermal protection is based on a calculated
model and it uses the output current of the drive to
determine the load on the motor. When the power
of the drive is turned on, the calculated model uses
the heatsink temperature to determine the initial
thermal stage for the motor. The calculated model
assumes that the ambient temperature of the motor
is 40°C.

Motor thermal protection can be adjusted by setting
the parameters. The  thermal current I

T

 specifies

the load current above which the motor is overloaded.
This current limit is a function of the output
frequency. The curve for I

T

 is set with parameters

7

.....

 6, 7

.....

 7 and 7

.....

 9, refer to the figure 6-26. The

parameters have their default values taken from the
motor name plate data.

With the output current at I

T

 the thermal stage will

reach the nominal value (100%). The thermal stage
changes by the square of the current. With output
current at 75% from I

T

 the thermal stage will reach

56% value and with output current at 120% from I

T

the thermal stage would reach 144% value. The
function will trip the device (refer par. 7

.....

 5) if the

thermal stage will reach a value of 105%. The speed
of change in thermal stage is determined with the
time constant parameter 7

.....

 8. The bigger the motor

the longer it takes to reach the final temperature.

The thermal stage of the motor can be monitored
through the display. Refer to the table for monitoring
items. (User's Manual, table 7.3-1).

CAUTION!

The calculated model does not protect the motor if the airflow to the

motor is reduced by blocked air intake grill.

7. 5

7. 5

7. 5

7. 5

7. 5

Motor thermal protection

Motor thermal protection

Motor thermal protection

Motor thermal protection

Motor thermal protection

Operation:

0 = Not in use
1 = Warning
2 = Trip function

Tripping and warning will display the same message code. If tripping is selected the
drive will stop and activate the fault stage.
Deactivating the protection, setting parameter to 0, will reset the thermal stage of
the motor to 0%.

7. 6

7. 6

7. 6

7. 6

7. 6

Motor thermal protection, break point current

Motor thermal protection, break point current

Motor thermal protection, break point current

Motor thermal protection, break point current

Motor thermal protection, break point current

The current can be set between 50.0—150.0% x I

nMotor

.

This parameter sets the value for thermal current at frequencies above the
break point on the  thermal current curve. Refer to the figure 6-26.
The value is set in percentage which refers to the name plate data of the
motor, parameter 1

.....

 13, nominal current of the motor, not the drive's nominal output

current.
The motor's nominal current is the current which the motor can withstand in direct
on-line use without being overheated.
If parameter 1

.....

 13 is adjusted, this parameter is automatically restored to the default

value.
Setting this parameter (or parameter 1

.....

 13) does not affect the maximum output

current of the drive. Parameter 1

.....

 7 alone determines the maximum output current

of the drive.

!

Содержание CX

Страница 1: ...VACON CX CXL CXS FREQUENCY CONVERTERS Multi purpose Control Application II USER S MANUAL Subject to changes without notice...

Страница 2: ...pose Multi purpose Multi purpose Multi purpose Multi purpose Control Application II Control Application II Control Application II Control Application II Control Application II par 0 1 0 CONTENTS CONTE...

Страница 3: ...GND I O ground Ground for reference and controls 4 Iin Analogue input Default setting not used 5 Iin current programmable range 0 20 mA 6 24V Control voltage output Voltage for switches etc max 0 1 A...

Страница 4: ...e 3 1 Control signal logic of the Multipurpose II Application Switch positions correspond to factory settings DIB4 DIB5 DIA1 DIB6 DIA2 P P P DIA3 UD012K05 1 DIB5 DIB6 Internal frequency reference Inte...

Страница 5: ...d parameters up to the panel possible only with graphical panel 5 Load down parameters from panel possible only with graphical panel 0 3 Language selection 0 2 1 0 0 English 1 Germany 2 Finnish Table...

Страница 6: ...lection 0 2 1 0 0 Linear 1 Squared 2 Programmable U f ratio 7 1 9 U f optimisation 0 1 1 0 0 None 1 Automatic torque boost 8 1 10 Nominal voltage of the motor 180 690 1 V 230 V 400 V 500 V 690 V Vacon...

Страница 7: ...to the set maximum frequency par 1 2 1 5 1 5 1 5 1 5 1 5 Reference selection Reference selection Reference selection Reference selection Reference selection 0 0 0 0 0 Analogue voltage reference from t...

Страница 8: ...ped 10 10 10 10 10 Same as setting 8 but the reference is stored to the memory over mains break When the value of the parameter 1 5 is set to 8 9 or 10 the values of the parameters 2 4 and 2 5 are aut...

Страница 9: ...anical noise Squared U f ratio can be used in applications where torque demand of the load is proportional to the square of the speed e g in centrifugal fans and pumps Un Par 6 4 Par 6 3 U V f Hz UD01...

Страница 10: ...Find this value fn on the rating plate of the motor This parameter sets the field weakening point parameter 6 3 to the same value 1 12 1 12 1 12 1 12 1 12 Nominal speed of the motor Nominal speed of...

Страница 11: ...C braking command 10 Multi step speed select 1 11 Selection between Iin and Uin 12 Run enable with coasting 13 Fieldbus control 14 Par 1 5 Uin 15 Par 1 5 Iin 22 2 4 DIB5 function terminal 15 0 13 1 1...

Страница 12: ...umscaling 320 00 0 0 01 0 no minimum scaling 23 320 00 2 17 Uin maximumscaling 320 00 100 0 01 100 no maximum scaling 23 320 00 2 18 Iin minimumscaling 320 00 0 0 01 0 no minimum scaling 23 320 00 2 1...

Страница 13: ...II Multi purpose Control Application II Multi purpose Control Application II Code Parameter Range Step Default Custom Description Page 2 28 Adjust Input 0 5 1 0 0 Not used 1 Voltage input 2 Current in...

Страница 14: ...6 3 6 Digital output function 0 22 1 1 0 Not used 1 Ready 2 Run 3 Fault 4 Fault inverted 5 Vacon overheat warning 6 External fault or warning 7 Reference fault or warning 8 Warning 9 Reversed 10 Joggi...

Страница 15: ...t 3 20 Frequency converter 10 75 C 1 C 40 C 28 temperature limit value 3 21 I O expander board opt 0 14 1 3 See parameter 3 1 analogue output content 3 22 I O expander board opt 0 01 10 s 0 01 1 00 Se...

Страница 16: ...1 Brake chopper in use 2 External brake chopper 4 6 Start function 0 1 1 0 0 Ramp 31 1 Flying start 4 7 Stop function 0 1 1 0 0 Coasting 31 1 Ramp 4 8 DC braking current 0 15 1 5 0 1 A 0 5 x InCX 31 x...

Страница 17: ...1 2 5 6 Prohibit frequency 0 fmax 0 1 Hz 0 Hz 0 Prohibit range 3 is off 33 range 3 high limit 1 2 Group 6 Motor control parameters Group 6 Motor control parameters Group 6 Motor control parameters Gro...

Страница 18: ...1 2 0 No action 36 1 Warning 2 Fault 7 6 Motor thermal protection 50 0 150 1 0 100 0 36 break point current x InMOTOR 7 7 Motor thermal protection 10 0 150 1 0 45 0 37 zero frequency current x InMOTO...

Страница 19: ...start function 1 Flying start 8 4 Automatic restart of 0 1 1 0 0 No 42 undervoltage 1 Yes 8 5 Automatic restart of 0 1 1 0 0 No 42 overvoltage 1 Yes 8 6 Automatic restart of 0 1 1 0 0 No 42 overcurre...

Страница 20: ...nction 0 1 0 1 0 Fieldbus control 44 term 301 fieldbus board 1 External fault 10 3 MODBUS Slave address 1 247 1 1 44 10 4 Baud rate 1 7 1 6 1 300 baud 44 2 600 baud 3 1200 baud 4 2400 baud 5 4800 baud...

Страница 21: ...Stop logic selection Start Stop logic selection Start Stop logic selection Start Stop logic selection 0 0 0 0 0 DIA1 closed contact start forward DIA2 closed contact start reverse See figure 6 1 DIA1...

Страница 22: ...art and Stop pulses are simultaneous the Stop pulse overrides the Start pulse DIA1 Start DIA2 Stop t min 50 ms UD009K12 FWD REV Output frequency DIA1 Start DIA2 Stop 2 2 2 2 2 DIA1 closed contact star...

Страница 23: ...ation time 1 selected time select contact closed Acceleration deceleration time 2 selected 5 5 5 5 5 Reverse contact open Forward Can be used for reversing if contact closed Reverse parameter 2 1 has...

Страница 24: ...purpose Control Application II Vacon Plc Phone 358 0 201 2121 Fax 358 0 201 212 205 Service 358 40 8371 150 E mail vacon vacon com t UD012K32 Param 4 10 DIA3 t UD012K32 DIA3 RUN STOP Output frequency...

Страница 25: ...on between I O and fieldbus control Note Note Note Note Note Par Par Par Par Par 2 3 2 4 2 5 2 3 2 4 2 5 2 3 2 4 2 5 2 3 2 4 2 5 2 3 2 4 2 5 In the fieldbus control par 10 1 1 and 10 2 0 2 6 2 6 2 6 2...

Страница 26: ...nput I Analogue input I Analogue input I Analogue input Iin in in in in inversion inversion inversion inversion inversion Parameter 2 14 0 no inversion of Iin input Parameter 2 14 1 inversion of Iin i...

Страница 27: ...2 21 2 21 2 21 Free analogue input signal Free analogue input signal Free analogue input signal Free analogue input signal Free analogue input signal function function function function function This...

Страница 28: ...ander Ain1 signal inversion I O Expander Ain1 signal inversion I O Expander Ain1 signal inversion I O Expander Ain1 signal inversion I O Expander Parameter 2 23 0 no inversion 2 24 2 24 2 24 2 24 2 24...

Страница 29: ...Input Adjust Input Range 0 5 Step 1 Default 0 Description 0 Not Used 1 Voltage Input 2 Current Input 3 AIN1 I O expand 4 AIN2 I O expand 5 FB signal 2 29 2 29 2 29 2 29 2 29 Adjust Precentage Adjust...

Страница 30: ...min output signal maximum set value Figure 6 14 Analogue output invert 3 4 3 4 3 4 3 4 3 4 Analogue output minimum Analogue output minimum Analogue output minimum Analogue output minimum Analogue outp...

Страница 31: ...ence limit supervision Reference goes outside of the set supervision Low limit High limit par 3 15 and 3 16 17 External brake control External brake ON OFF control with programmable de lay par 3 17 an...

Страница 32: ...put or the panel reference if panel is the active control source 3 16 3 16 3 16 3 16 3 16 Reference limit supervision value Reference limit supervision value Reference limit supervision value Referenc...

Страница 33: ...filter time 3 22 I O expander board opt analogue output filter time 3 22 I O expander board opt analogue output filter time 3 22 I O expander board opt analogue output filter time 3 22 I O expander b...

Страница 34: ...29 3 29 3 29 3 29 3 29 Digital output DO1 off delay Digital output DO1 off delay Digital output DO1 off delay Digital output DO1 off delay Digital output DO1 off delay 3 30 3 30 3 30 3 30 3 30 Relay o...

Страница 35: ...4 1 4 1 4 1 4 1 Acc Dec ramp 1 shape Acc Dec ramp 1 shape Acc Dec ramp 1 shape Acc Dec ramp 1 shape Acc Dec ramp 1 shape 4 2 4 2 4 2 4 2 4 2 Acc Dec ramp 2 shape Acc Dec ramp 2 shape Acc Dec ramp 2 sh...

Страница 36: ...that of acceleration if the brake resistor is selected correctly See separate Brake resistor installation manual 4 6 4 6 4 6 4 6 4 6 Start function Start function Start function Start function Start...

Страница 37: ...on the motor can be electrically stopped in the shortest possible time without using an optional external braking resistor The braking time is scaled according to the frequency when the DC braking sta...

Страница 38: ...p speed references 1 7 Multi Step speed references 1 7 Multi Step speed references 1 7 Parameter value defines the Multi Step speeds selected with the digital inputs 5 1 5 1 5 1 5 1 5 1 Prohibit frequ...

Страница 39: ...arameters 1 8 1 9 6 5 6 6 and 6 7 See figure 6 25 When the parameters 1 10 and 1 11 nominal voltage and nominal frequency of the motor are set also parameters 6 3 and 6 4 are set automatically to the...

Страница 40: ...xternal fault Response to external fault Response to external fault 0 No response 1 Warning 2 Fault stop mode after fault according to parameter 4 7 3 Fault stop mode after fault always by coasting A...

Страница 41: ...bigger the motor the longer it takes to reach the final temperature The thermal stage of the motor can be monitored through the display Refer to the table for monitoring items User s Manual table 7 3...

Страница 42: ...rameters 1 12 and 1 13 If either of these parameters is set this parameter is set to default value If the motor s t6 time is known given by the motor manufacturer the time constant 7 8 7 8 7 8 7 8 7 8...

Страница 43: ...92 Trip area Motor temperature Time Motor temperature Time constant T Changed with motor size and adjusted with parameter 7 8 Trip warning Motor current Parameters 7 10 7 13 Stall protection Parameter...

Страница 44: ...ral General General The purpose of motor underload protection is to ensure that there is load on the motor when the drive is running If the motor loses its load there might be a problem in the process...

Страница 45: ...weakening area load Underload protection field weakening area load Underload protection field weakening area load The torque limit can be set between 20 0 150 x TnMotor This parameter gives the value...

Страница 46: ...o action 1 Warning 2 Fault The thermistor connected to the thermistor input of the I O expander board supervises the temperature of the motor With parameter 7 19 the response of the frequency converte...

Страница 47: ...urns to normal condition DC link voltage returns to the normal level 8 5 8 5 8 5 8 5 8 5 Automatic restart after overvoltage trip Automatic restart after overvoltage trip Automatic restart after overv...

Страница 48: ...erence scaling bias orque reference scaling bias orque reference scaling bias orque reference scaling bias orque reference scaling bias 9 3 9 3 9 3 9 3 9 3 T T T T Torque reference scaling gain orque...

Страница 49: ...ly for Modbus protocol Parameters 10 3 10 6 only for Modbus protocol Parameters 10 3 10 6 only for Modbus protocol Parameters 10 3 10 6 only for Modbus protocol Parameters 10 3 10 6 only for Modbus pr...

Страница 50: ...10 10 10 10 10 Profibus process Data 1 Profibus process Data 1 Profibus process Data 1 Profibus process Data 1 Profibus process Data 1 10 1 10 1 10 1 10 1 10 11 1 1 1 1 Profibus process Data 2 Profib...

Страница 51: ...nter programmable button 3 V11 MW hours MWh Total MW hours not resettable V12 MW hours MWh MW hours can be reset with programmable trip counter button 4 V13 Voltage analogue input V Voltage of the ter...

Страница 52: ...e 7 65381 VAASA FINLAND Tel 358 0 201 2121 Fax 358 0 201 212 205 Service 358 40 8371 150 E mail vacon vacon com Ud00182d 09 10 2000 Author Jaana Kukkonen email jaana kukkonen vacon com fax 358 0 201 2...

Отзывы: