Page 11
Multi-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application II
Vacon Plc
Phone:
+358-(0)201 2121
Fax: +358-(0)201 212 205
Service:
+358-40-8371 150
E-mail: [email protected]
Code
Parameter
Range
Step
Default
Custom
Description
Page
2. 6
U
in
signal range
0—2
1
0
0 = 0—10 V
1 = Custom setting range
2 = -10—+10 V (can be used with
Joystick control only)
2
.
.
.
.
.
7
U
in
custom setting min.
0—100%
0.01%
0.00%
22
2
.
.
.
.
.
8
U
in
custom setting max.
0—100%
0.01%
100.00%
22
2
.
.
.
.
.
9
U
in
signal inversion
0—1
1
0
0 = Not inverted
22
1 = Inverted
2
.....
10
U
in
signal filter time
0 —10s
0.01s
0.1s
0 = No filtering
22
2
.....
11
I
in
signal range
0—2
1
0
0 = 0—20 mA
23
1 = 4—20 mA
2 = Custom setting range
2
.....
12
I
in
custom setting minim.
0—100%
0.01%
0.00%
23
2
.....
13
I
in
custom setting maxim.
0—100%
0.01% 100.00%
23
2
.....
14
I
in
signal inversion
0—1
1
0
0 = Not inverted
23
1 = Inverted
2
.
.
.
.
.
15
I
in
signal filter time
0 —10s
0.01s
0.1s
0 = No filtering
23
2
.....
16
U
in
minimum scaling
-320,00%—
0%
0,01
0% = no minimum scaling
23
+320,00 %
2
.....
17
U
in
maximum scaling
-320,00%—
100%
0,01
100% = no maximum scaling
23
+320,00 %
2
.....
18
I
in
minimum scaling
-320,00%—
0%
0,01
0% = no minimum scaling
23
+320,00 %
2
.....
19
I
in
maximum scaling
-320,00%—
100%
0,01
100% = no maximum scaling
23
+320,00 %
2
.
.
.
.
.
20
Free analogue input,
0—5
1
0
0 = Not use
24
signal selection
1 = U
in
(analogue voltage input)
2 = I
in
(analogue current input)
3 = Ain1 (option board)
4 = Ain2 (option board)
5 = Fieldbus signal
2
.....
21
Free analogue input,
0—4
1
0
0 = No function
24
function
1 = Reduces current limit
(par. 1
.....
7)
2 = Reduces DC-braking current
3 = Reduces acc. and decel. times
4 = Reduces torque supervis. limit
2
.....
22
Motorised potentiometer
0.1—2000.0
0.1
10.0
25
ramp time
Hz/s
Hz/s
Hz/s
2
.
.
.
.
.
23
Option board Ain1 signal
0—1
1
0
0 = Not inverted
25
inversion
1 = Inverted
2
.....
24
Option board Ain1 signal
0—10s
0.01s
0.1s
0 = No filtering
25
filter time
2
.....
25
Option board Ain2 signal
0—2
1
0
0 = 0—20 mA
25
signal range
1 = 4—20 mA
2 = 0—10 V
2
.....
26
Option board Ain2 signal
0—1
1
0
0 = Not inverted
25
inversion
1 = Inverted
2
.
.
.
.
.
27
Option board Ain2 signal
0 —10s
0.01s
0.1s
0 = No filtering
25
filter time
Note!
Note!
Note!
Note!
Note!
STOP
STOP
STOP
STOP
= Parameter value can be changed only when the frequency converter is stopped. (Continues)