general data
vacon
•
59
24-hour s358 (0)201 212 575 • Email: [email protected]
7
Note 1:
The input currents are calculated values with 100 kVA line transformer sup-
ply.
Note 2:
For PM engine, please select the drive power rating according to engine shaft
power, not rated current.
Quick Modbus setup
Mains voltage 600 V, 50/60 Hz, 3~ series
Fre-
quency
converter
type
Rated loadability
Motor shaft
power
Nominal
input cur-
rent
Mechanical
size
Weight
(kg)
100% continu-
ous current
I
N
[A]
150% over-
load current
[A]
P
[HP]
P
[KW]
[A]
0002
1.7
2.6
1
0.75
2
MI3
0.99
0003
2.7
4.2
2
1.5
3.6
MI3
0.99
0004
3.9
5.9
3
2.2
5
MI3
0.99
0006
6.1
9.2
5
4
7.6
MI3
0.99
0009
9
13.5
7.5
5.5
10.4
MI3
0.99
Table 5: Vacon 20 power ratings, 600 V
1
A: Select Fieldbus as remote control place: P2.1 to1 – Fieldbus
B: Set Modbus RTU protocol to “ON:” SYS P2.2 to 1 – Modbus
2
A. Set Control Word to “0” (2001)
B. Set Control Word to “1” (2001)
C. Frequency converter status is RUN
D. Set Reference value to “5000” (50.00%) (2003)
E. Actual Speed is 5000 (25.00 Hz if MinFreq is 0.00 Hz and MaxFreq is 50.00 Hz)
F. Set Control Word to “0” (2001)
G. Frequency converter status is STOP