monitoring & parameters
vacon
•
35
24-hour s358 (0)201 212 575 • Email: [email protected]
5
5.9 Pulse train/Encoder (Control panel: Menu PAR -> P7)
Code
Parameter
Min
Max
Unit
Default
ID
Note
P7.1
Min pulse fre-
quency
0
10000
Hz
0
1229
Pulse frequency to be
interpreted as a 0% sig-
nal.
P7.2
Max pulse fre-
quency
0.0
10000
Hz
10000
1230
Pulse frequency to be
interpreted as a 100%
signal.
P7.3
Freq ref at min
pulse freq
0.00
P3.2
Hz
0.00
1231
Frequency corresponds
to 0% if used as fre-
quency reference.
P7.4
Freq ref at max
pulse freq
0.00
P3.2
Hz
50.00 /
60.00
1232
Frequency corresponds
to 100% if used as fre-
quency reference.
P7.5
Encoder direc-
tion
0
2
0
1233
0
= Disable
1
= Enable/Normal
2
= Enable/Inverted
P7.6
Encoder pulses /
revolution
1
65535
ppr
256
629
Pulse count of encoder
per round. Used to scale
encoder rpm monitor
value only.
Config DI5 and
DI6
0
2
0
1165
0
= DI5 and DI6 are for
normal digital input
1
= DI6 is for pulse train
2
= DI5 and DI6 are for
encoder frequency mode
Table 9: Pulse train/Encoder
P7.7
Содержание 20
Страница 1: ...vacon 20 ac drives quick guide...
Страница 2: ......
Страница 15: ...installation vacon 13 24 hour support 358 0 201 212 575 Email vacon vacon com 2 2 3 4...
Страница 16: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 2 5 6...