- The drive can be connected to the power supply with the above-mentioned fuses.
The short circuit current of the power supply cannot exceed 50 kA
- Use cables with heat resistance of at least +70 °C.
- The fuses also function as cable overload protection.
- These instructions only apply to cases with one motor and one cable connection
from the frequency converter to the motor.
- In order to comply with standard EN61800-5-1, the protective conductor should be
at least 10 mm
2
Cu or 16 mm
2
Al
. Another option is to use an additional protective
conductor of at least the same size as the original one.