18
•
vacon
navigation & startup
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
4
4.2 Putting into operation and startup wizard
4.2.1 Steps to put the drive into operation:
4.2.2 Startup wizard
Vacon 20 runs the startup wizard when the machine is powered up for the first time.
The wizard is run by setting SYS Par.4.2 =1. The following figures show the proce-
dure.
NOTE: Running the startup wizard always returns all parameters to
their factory default settings.
NOTE! StartUp-Wizard can be skipped after pressing the STOP button
continuously for 30 seconds
1. Read the safety instructions on page 1
7. Perform the test run
without the motor
; see
the User Manual at www.vacon.com
2. Secure the grounding and check that cables
comply with requirements
8. Run no-load tests without the motor con-
nected to the process
3. Check the quality and quantity of the cooling
air
9. Perform an identification run (Par. ID631)
4. Check that all start/stop switches are in the
STOP
position
10. Connect the motor to the process and per-
form the test run again
5. Connect the drive to the mains
11. Vacon 20 is now ready for use
6. Run the startup wizard and set all necessary
parameters
Table 1: Steps to put the drive into operation