5
5.5 Frequency references (Control panel: Menu PAR -> P3)
NOTE:
These parameters display when P17.2 = 0.
Code
Parameter
Min
Max
Unit
Default
ID
Note
Min frequency
0.00
P3.2
Hz
0.00
101
Minimum allowed fre-
quency reference
Max frequency
P3.1
320.00
Hz
50.00 /
60.00
102
Maximum allowed fre-
quency reference
P3.3
Remote Control
Place 1 fre-
quency refer-
ence selection
1
Varies
7
117
1
= Preset speed 0
2
= Keypad
3
= Fieldbus
4
= AI1
5
= AI2
6
= PID
7
= AI1 + AI2
8
= Motor potentiometer
9
= Pulse train/Encoder
10
= AIE1
11
= Temperature input 1
12
= Temperature input 2
13
= Temperature input 3
Note: Pay attention to DI/
Encoder switch position
when set with 9=Pulse
train / Encoder
P3.4
Preset speed 0
P3.1
P3.2
Hz
5.00
180
Preset speed 0 is used as
frequency reference when
P3.3 = 1
P3.5
Preset speed 1
P3.1
P3.2
Hz
10.00
105 Activated by digital inputs
P3.6
Preset speed 2
P3.1
P3.2
Hz
15.00
106 Activated by digital inputs
P3.7
Preset speed 3
P3.1
P3.2
Hz
20.00
126 Activated by digital inputs
P3.8
Preset speed 4
P3.1
P3.2
Hz
25.00
127 Activated by digital inputs
P3.9
Preset speed 5
P3.1
P3.2
Hz
30.00
128 Activated by digital inputs
P3.10
Preset speed 6
P3.1
P3.2
Hz
40.00
129 Activated by digital inputs
P3.11
Preset speed 7
P3.1
P3.2
Hz
50.00
130 Activated by digital inputs
P3.12
Remote Control
Place 2 fre-
quency refer-
ence selection
1
Varies
5
131 See P3.3
P3.13
Motor Potenti-
ometer Ramp
1
50
Hz/s
5
331 Speed variation rate
P3.14
Motor Potenti-
ometer Reset
0
2
2
367
0
= No Reset
1
= Reset if stopped
2
= Reset if powered down
Table 5: Frequency references
P3.1
P3.2