6
vacon • 44
Communications
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Reply frame:
6.5.3
Example 3 - Exception response
In an exception response, the Slave sets the
most-significant bit (MSB)
of the function code to 1.
The Slave returns an exception code in the data field.
Command Master - Slave:
Message frame:
Exception response:
Answer Slave - Master:
Reply frame:
Table 43.
01 04 04
13 88 09 C4 78 E9
Table 44.
ADDRESS
01 hex
Slave address 1 hex (= 1)
FUNCTION
04 hex
Function 4 hex (= 4)
DATA
Starting address HI 17 hex
Starting address 1770 hex (= 6000)
Starting address LO 70 hex
No. of registers HI
00 hex
Invalid number of registers 0005 hex (= 5)
No. of registers LO
05 hex
ERROR
CHECK
CRC HI
34 hex
CRC field 3466 hex (=13414)
CRC LO
66 hex
Table 45.
01 04 17
70 00 05
34 66
Table 46.
ADDRESS
01 hex
Slave address 1 hex (= 1)
FUNCTION
84 hex
Most significant bit set to 1
DATA
Error
code
04 hex
Error code 04 => Slave Device Failure
ERROR
CHECK
CRC HI 42 hex
CRC field 42C3 hex (= 17091)
CRC LO C3 hex
Table 47.
01 84 04
42 C3
Содержание 100 INDUSTRIAL
Страница 2: ......