Communications
vacon • 31
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6
6.3
Modbus data mapping
6.3.1
Coils registers
A "coil" in Modbus is a single-bit binary data item which can be both read and written. In VACON
®
100 family AC drives, the coils refer to some bits in the fieldbus control word." See page 34.
6.3.2
Clearing resettable counters
The VACON
®
AC drives have trip counters for operation days and energy. These counters can be
reset to zero by writing value '1' to addresses defined in table below. You can also use coils defined
in chapter 6.3.1.
6.3.3
Discrete inputs
A "discrete input" in Modbus is a single-bit binary data item which is read-only. In VACON
®
100
family AC drives, the discrete inputs refer to the fieldbus status word bits
.
See Chapter 10.
Table 16.
Defined coil registers
Address
Function
Purpose
0001
RUN/STOP
Control Word, bit 0
0002
Direction
Control Word, bit 1
0003
Fault reset
Control Word, bit 2
0017
Reset
Clears operation days trip counter
0018
Reset
Clears energy trip counter
Table 17. Clearing trip counters
Address
Function
Purpose
40101
Reset
Clears operation days trip counter
40301
Reset
Clears energy trip counter
Table 18.
Defined Input Discrete
Address
Function
Purpose
10001
Ready
Status Word, bit 0
10002
Run
Status Word, bit 1
10003
Direction
Status Word, bit 2
10004
Fault
Status Word, bit 3
10005
Alarm
Status Word, bit 4
10006
At reference
Status Word, bit 5
10007
Zero speed
Status Word, bit 6
10008
Flux ready
Status Word, bit 7