6
vacon • 38
Communications
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6.3.11
Energy counter
This counter holds the value of total amount of energy taken from a supply network. This counter
cannot be reset. The values are read only.
Energy counter as kWh
This counter is in registers 40211d to 40212d and is a 32-bit floating point (IEEE 754) value
containing the number of kilowatt-hours (kWh) that is in the drive's energy counter. This value is
read-only.
Energy counter
These registers hold three values for the energy counter, amount of energy used, format of the
energy value and unit of the energy value.
Example:
If energy = 1200, format = 52, unit = 1, then actual energy is 12.00 kWh.
Table 29. Energy counter as kWh
Address
Description
40211 High data
40212 Low data
Holds the value of energy counter in
kWh. Datatype is 32 bit float IEEE 754
Table 30. Energy counter
Holding register
address
Input register
address
Purpose
Description
40201
201
Energy
Amount of energy taken from a supply
network.
40202
202
Format
The last number of the Format field indi-
cates the decimal point place in the
Energy field.
Example:
40 = 4 number of digits, 0 fractional digits
41 = 4 number of digits, 1 fractional digit
42 = 4 number of digits, 2 fractional digits
40203
203
Unit
1 = kWh
2 = MWh
3 = GWh
4 = TWh
Unit of the value.