Fiedlbus parametrization
vacon • 27
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5
5.3
Modbus TCP/UDP parameters and monitoring values
5.3.1
Ethernet common settings (M5.9.1)
5.3.2
IP Address mode
Selectable alternatives are DHCP (Dynamic Host Configuration Protocol) and Fixed. The DHCP
protocol gives IP addresses to new devices connecting to local network. This address is valid for a
certain period of time. If no DHCP server is found, an automatic random IP is given. A fixed IP
address is specified manually and it does not change. When the mode is changed from DHCP to
Fixed the addresses will read:
IP: 192.168.0.10
Subnet mask: 255.255.0.0
Default gateway: 192.168.0.1
5.3.3
Fixed IP address
An IP address is a series of numbers (like above) specific to the device connected to the Internet.
Table 12. Ethernet common settings (M5.9.1)
Panel
Tree
Parameter
Range
Default
ID
Description
P5.9.1.1
IP address mode
Fixed (1),
DHCP(2)
DHCP (2)
2482 IP Mode
P5.9.1.2
Duplicate IP
Detection
Disabled (0),
Enabled (1)
enabled
2569
This is setting for enabling
ACD (See Chapter 3.4).
When disabled drive does
not check for or react to
address conflict situation.
P5.9.1.3.1 IP address
1.0.0.0 -
223.255.255.255
192.168.0.10 2529 Fixed IP address
P5.9.1.3.2 Subnet mask
0.0.0.0-
255.255.255.255
255.255.0.0
2530 Fixed Subnet mask
P5.9.1.3.3 Default gateway
0.0.0.0-
255.255.255.255
192.168.0.1
2531 Fixed default gateway
P5.9.1.4
Active IP address
-
-
2483
Shows current active IP
address. It is same as fixed
value if IP mode is "Fixed".
P5.9.1.5
Active subnet
mask
-
-
2484
Shows current active sub-
net mask. It is same as fixed
value if IP mode is "Fixed".
P5.9.1.6
Active default
gateway
-
-
2485
Shows current active default
gateway. It is same as fixed
value if IP mode is "Fixed".
P5.9.1.7
MAC address
-
-
2486 Drive MAC address
Содержание 100 INDUSTRIAL