Fiedlbus parametrization
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Only messages to the current slave in use are counted in the good messages.
5.2.10
Illegal functions
This value counts error situations. The function code received in the query refers to a not allowed
action for the server (or slave). This corresponds to Modbus fault code 01h.
5.2.11
Illegal data addresses
This value counts error situations. The data address received in the query refers to not allowed
address for the server (or slave). This corresponds to Modbus fault code 02h.
5.2.12
Illegal data values
This value counts error situations. A value contained in the query data field refers to a not allowed
value for server (or slave). This corresponds to Modbus fault code 03h.
5.2.13
Slave device busy
This value counts error situations. The server (or slave) is engaged in processing a long-duration
program command. The client (or master) should retransmit the message later when the server (or
slave) is free. This corresponds to Modbus fault code 06h.
5.2.14
Memory parity error
This value counts error situations. The server (or slave) attempted to read record file but detected
a parity error in the memory. This corresponds to Modbus fault code 08h.
5.2.15
Slave device failure
This value counts error situations. An unrecoverable error occurred while the server (or slave) was
attempting to perform the requested action. This corresponds to Modbus fault code 04h.
5.2.16
Last fault response
Shows the last fault response as Fault code.
5.2.17
Control word
Shows the Control Word received from the bus.
5.2.18
Status word
Shows the current Status Word that is sent to the bus.
Table 11. Communication status description
Good messages
0…999
Number of messages received without errors
Bad messages
0…99
Number of messages received with errors