Fiedlbus parametrization
vacon • 23
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5
5.1.2
Enabling Modbus protocol
Modbus TCP/UDP is always enabled in VACON
®
100 family devices. You need to parametrize the
network settings (IP address etc) before using it. See Chapter 5.3.1.
When using Modbus RTU, you need to enable the protocol. After enabling it, protocol settings will
appear under panel tree P5.8.3.
5.2
Modbus RTU parameters and monitoring values (M5.8.3)
* This feature is not supported in VACON
®
100 HVAC. The default application in the VACON
®
100
family AC drives supports only Slave mode. A special application is required for Master functionality.
Table 5. Enabling Modbus RTU protocol
Parameter name
ID
Value
Default
Panel Tree
RS-485 protocol
2208
0 = No Protocol
1 = Modbus RTU
2 = BACnet MSTP
3 = N2
No protocol
P 5.8.1.1
Table 6. Parameters related with Modbus used through RTU
Panel Tree
Parameter
Range
Default
ID
Description
P5.8.3.1.1
Slave address
1…247
1
2320
Unique slave device
address.
P5.8.3.1.2
Baud rate
300…230400
6
2378
Communication speed
300
600
1200
2400
4800
9600
19200
38400
57600
76800
115200
230400
P5.8.3.1.4
Stopbits
1…3
3
2380
1 = 1 stop bit
2 = 1.5 stop bits
3 = 2 stop bits
P5.8.3.1.3
Parity type
0…2
0
2379
0 = Even
1 = Odd
2 = None
P5.8.3.1.5
Communication
time-out
0…65535
10
2321
Unit is seconds
0 = Not used
P5.8.3.1.6 *
Operate Mode
0…1
0
2374
0 = Slave
1 = Master
P5.8.3.1.7.1-
30
IDMap IDs
0…65535
0
3130-
3159
IDMap IDs
Содержание 100 INDUSTRIAL
Страница 2: ......